Loading Port:Ningbo
Payment Terms:TT OR LC
Min Order Qty:100 pc
Supply Capability:5000 pc/month
The Deye 70-110K grid-connected inverter is suited for medium and large-scale commercial rooftops and ground-mounted solar PV system in which reliability and stability are important. the full series inverter has 30% DC input oversizing ratio and 10% AC output overloading ratio, offering a faster return on investment.
Max. 6 MPP trackers, Max. efficiency up to 98.7%
Zero export application, VSG application
String intelligent monitoring (optional)
Wide output voltage range
Type II DC/AC SPD
Anti-PID function (Optional)
Model | SUN-70K-G03 | SUN-75K-G03 | SUN-80K-G03 | SUN-90K-G03 | SUN-100K-G03 | SUN-110K-G03 | ||
Input Side | ||||||||
Max. DC Input Power (kW) | 91 | 97.5 | 104 | 135 | 150 | 150 | ||
Max. DC Input Voltage (V) | 1000 | |||||||
Start-up DC Input Voltage (V) | 250 | |||||||
MPPT Operating Range (V) | 200~850 | |||||||
Max. DC Input Current (A) | 40+40+40+40 | 40+40+40+40+40+40 | ||||||
Max. Short Circuit Current (A) | 60+60+60+60 | 60+60+60+60+60+60 | ||||||
Number of MPPT / Strings per MPPT | 4/4 | 6/4 | ||||||
Output Side | ||||||||
Rated Output Power (kW) | 70 | 75 | 80 | 90 | 100 | 110 | ||
Max. Active Power (kW) | 77 | 82.5 | 88 | 99 | 110 | 121 | ||
Nominal Output Voltage / Range (V) | 3L/N/PE 380V/0.85Un-1.1Un, 400V/0.85Un-1.1Un | |||||||
Rated Grid Frequency (Hz) | 50 / 60 (Optional) | |||||||
Operating Phase | Three phase | |||||||
Rated AC Grid Output Current (A) | 101.5 | 108.7 | 115.9 | 130.4 | 144.9 | 159.4 | ||
Max. AC Output Current (A) | 111.6 | 119.6 | 127.5 | 143.5 | 159.4 | 175.4 | ||
Output Power Factor | >0.99 | |||||||
Grid Current THD | <3% | |||||||
DC Injection Current (mA) | <0.5% | |||||||
Grid Frequency Range | 47~52 or 57~62 (Optional) | |||||||
Efficiency | ||||||||
Max. Efficiency | 98.7% | |||||||
Euro Efficiency | 98.3% | |||||||
MPPT Efficiency | >99% | |||||||
Protection | ||||||||
DC Reverse-Polarity Protection | Yes | |||||||
AC Short Circuit Protection | Yes | |||||||
AC Output Overcurrent Protection | Yes | |||||||
Output Overvoltage Protection | Yes | |||||||
Insulation Resistance Protection | Yes | |||||||
Ground Fault Monitoring | Yes | |||||||
Anti-islanding Protection | Yes | |||||||
Temperature Protection | Yes | |||||||
Integrated DC Switch | Yes | |||||||
Remote software upload | Yes | |||||||
Remote change of operating parameters | Yes | |||||||
Surge protection | DC Type II / AC Type II | |||||||
General Data | ||||||||
Size (mm) | 838W×568H×323D | |||||||
Weight (kg) | 73.7 | |||||||
Topology | Transformerless | |||||||
Internal Consumption | <1W (Night) | |||||||
Running Temperature | -25~65℃, >45℃ derating | |||||||
Ingress Protection | IP65 | |||||||
Noise Emission (Typical) | <55 dB | |||||||
Cooling Concept | Smart cooling | |||||||
Max. Operating Altitude Without Derating | 2000m | |||||||
Warranty | 5 years | |||||||
Grid Connection Standard | CEI 0-21, VDE-AR-N 4105, NRS 097, IEC 62116, IEC 61727, G99, G98, VDE 0126-1-1, RD 1699, C10-11 | |||||||
Operating Surroundings Humidity | 0-100% | |||||||
Safety EMC / Standard | IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2 | |||||||
Features | ||||||||
DC Connection | MC-4 mateable | |||||||
AC Connection | IP65 rated plug | |||||||
Display | LCD 240 × 160 | |||||||
Interface | RS485/RS232/Wifi/LAN |