Loading Port:Ningbo
Payment Terms:TT OR LC
Min Order Qty:100 pc
Supply Capability:5000 pc/month
This series inverter is specially designed for 127/220Vac three-phase system, providing rated power at 35KW, 40KW, 45KW, 50KW. Equipped with large LCD and buttons, easy to operate and maintenance. With compact design and high-power density, this series supports 1.3 DC/AC ratio, saving device investment.
127/220Vac and 60Hz, three phase system
4 MPP tracker, Max. efficiency up to 98.7%
Zero export application, VSG application
String intelligent monitoring (optional)
Wide output voltage range
Type II DC/AC SPD
Anti-PID function (Optional)
Technical Data | ||||||
Model | SUN-35K-G02-LV | SUN-40K-G-LV | SUN-45K-G-LV | SUN-50K-G-LV | ||
Input Side | ||||||
Max. DC Input Power (kW) | 45.5 | 52 | 58.5 | 65 | ||
Max. DC Input Voltage (V) | 800 | |||||
Start-up DC Input Voltage (V) | 250 | |||||
MPPT Operating Range (V) | 200~700 | |||||
Max. DC Input Current (A) | 30+30+30+30 | 40+40+40+40 | ||||
Max. Short Circuit Current (A) | 45+45+45+45 | 60+60+60+60 | ||||
Number of MPPT / Strings per MPPT | 4/3 | 4/4 | ||||
Output Side | ||||||
Rated Output Power (kW) | 35 | 40 | 345 | 50 | ||
Max. Active Power (kW) | 38.5 | 44 | 49.5 | 55 | ||
Nominal Output Voltage / Range (V) | 3L/N/PE 127/0.85Un-1.1Un,220 /0.85Un-1.1Un (this may vary with grid standards) | |||||
Rated Grid Frequency (Hz) | 60 / 50 (Optional) | |||||
Operating Phase | Three phase | |||||
Rated AC Grid Output Current (A) | 91.9 | 104.9 | 118.1 | 131.2 | ||
Max. AC Output Current (A) | 101.1 | 115.5 | 129.9 | 144.4 | ||
Output Power Factor | 0.8 leading to 0.8 lagging | |||||
Grid Current THD | <3%< span=""> | |||||
DC Injection Current (mA) | <0.5%< span=""> | |||||
Grid Frequency Range | 57~62 | |||||
Efficiency | ||||||
Max. Efficiency | 98.7% | |||||
Euro Efficiency | 98.3% | |||||
MPPT Efficiency | >99% | |||||
Protection | ||||||
DC Reverse-Polarity Protection | Yes | |||||
AC Short Circuit Protection | Yes | |||||
AC Output Overcurrent Protection | Yes | |||||
Output Overvoltage Protection | Yes | |||||
Insulation Resistance Protection | Yes | |||||
Ground Fault Monitoring | Yes | |||||
Anti-islanding Protection | Yes | |||||
Temperature Protection | Yes | |||||
Integrated DC Switch | Yes | |||||
Remote software upload | Yes | |||||
Remote change of operating parameters | Yes | |||||
Surge protection | DC Type II / AC Type II | |||||
General Data | ||||||
Size (mm) | 700W×575H×297D | |||||
Weight (kg) | 60 | |||||
Topology | Transformerless | |||||
Internal Consumption | <1W (Night) | |||||
Running Temperature | -25~65℃, >45℃ derating | |||||
Ingress Protection | IP65 | |||||
Noise Emission (Typical) | <55 dB | |||||
Cooling Concept | Smart cooling | |||||
Max. Operating Altitude Without Derating | 2000m | |||||
Warranty | 5 years | |||||
Grid Connection Standard | CEI 0-21, VDE-AR-N 4105, NRS 097, IEC 62116, IEC 61727, G99, G98, VDE 0126-1-1, RD 1699, C10-11 | |||||
Operating Surroundings Humidity | 0-100% | |||||
Safety EMC / Standard | IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2 | |||||
Features | ||||||
DC Connection AC Connection Display Interface | MC-4 mateable IP65 rated plug LCD 240 × 160 RS485/RS232/Wifi/LAN | |||||
AC Connection | IP65 rated plug | |||||
Display | LCD 240 × 160 | |||||
Interface | RS485/RS232/Wifi/LAN |