Loading Port:China main port
Payment Terms:TT OR LC
Min Order Qty:500 m
Supply Capability:50000 m/month
STA/SWA/AWA armour High voltage XLPE cable
General Conditions
Rated Voltage: 3.6/6kv,6/10(11)kv,8.7/10(15)kv,12/20(24)KV,18/30(33)kv,26/35kv.
Conductor: Cu or Al.
Insulation: XLPE.
Armor: (Stainless)Steel tape armored,(Stainless) steel wire armored,Aluminum wire armored.
Jacket: PVC/PE
Usage: Construction,underground
Standard: IEC0502,IEC60228 for conductor,other standards allowed.
1.Usage
This product is suitable for use in rated AC voltage (U0/U)6/6-26/35KV system transmitting and
distributing lines.According to different sheath make ups,they can be used for laying in the air(cable bridges,indoor well supports and groove boxes) and in soil (direct burying,cable canals
and pipe lines,etc).
2.Properties and functions
For XLPE insulated power cable,either chemical method or physical method had been employed to transform the
molecular structure of PE from linear chain into three dimensional network,that is thermoplastic PE had
been transformed into thermosetting XLPE.
After crosslinking,the heat mechanical properties of the cable have been greatly improved while its excellent electrical
properties are still maintained.
The nominal conductor operating temperature of XLPE insulated power cable is 90 degrees.
The cable has the advantages of simplicity in construction,lightness in weight beside its excellent electrical,heat mechanical and anti-chemical corrosion properties.
It can also be laid with no limitation of level difference along the route.
3.Properties of applications
1).Max.permissible continuous operating temperature f conductor of 6~35KV cable shall not exceed 90 degrees.
2).Conductor short circuit temperature should not be exceed 250degrees. Max.sustaining period not exceed 5 seconds.
3).Bending radius:
a).Bending radius of single core cable:20(d+D)±5%.
b).Bending radius of multi-core cable:15(d+D)±5%.
c).D is actual outer diameter of cable sample(mm),d is actual diameter of the conductor(mm).
4).Not restricted by the difference of level along the route.
5).Insulation temperature:it should be heated while ambient temperature is below 0 degree.