Rated Voltage 1KV or Lower ACSR Conductor Insulated Overhead Cable
Application for Rated Voltage Conductor Cable
It is used for AC rated voltage(U) is 1 KV or lower overhead power lines, with ACSR conductor, weatherable PVC, PE, or XLPE insulated aerial cables.
Type & Specification for Rated Voltage Conductor Cable
Voltage | 1 kV |
Type | JKLGV、JKLGY、JKLGYJ |
Size(mm2) | 1 Core :10~400; 2~4 Core:10~120 |
Standard | Q/XLJ 0341 |
Using Feature of Rated Voltage Conductor Cable
Allowable long-term working temperature of cable conductor: PVC, polyethylene insulation should not exceed 70 ℃; XLPE insulation should not exceed 90 ℃.
Cable laying temperature not lower than -20 ℃.
Cable bending radius:
cable which diameter (D)less than 25mm, the bending radius shall be not less than 4D; cable which diameter(D) more than 25mm, the bending radius shall not be less than 6D.
Structure for Rated Voltage Conductor Cable
Picture