It is suitable for power grid with rated voltage 0.6/1kV or the power transmission in the power equipment.
The highest environment permissible continuous operating temperature for the conductor of the PVC Insulating Power Cable to work normally is 70℃. In case of short circuit (with duration less than 5 seconds), the highest temperature of the conductor is less than 160℃.
The ambient temperature under installation should not be below 0℃.
The recommended bending radius: for mono-core cable, not less than 20 times of the cable's actual external diameter; for multi-core cable, not less than 15 times of the cable's actual external diameter.
Type and designation: | |
Type Designation range of cable VVCopper Conductor PVC Insulating PVC Jacket Power Cable (Rated Voltage 0.6/1kV)1、2、3、4、5、3+1、4+1、3+2cores1.5~185mm2VLVAluminum Conductor PVC Insulating PVC Jacket Power Cable (Rated Voltage 0.6/1kV) VV22Copper Conductor PVC Insulating Steel Tape Armored PVC Jacket Power Cable (Rated Voltage 0.6/1kV) VLV22Aluminum Conductor PVC Insulating Steel Tape Armored PVC Jacket Power Cable (Rated Voltage 0.6/1kV) |
m.cross-section of conductor | Structure of conductor | Insulation | Max.d.c resistance at 20℃ | Min. insulation resistance constant at 20℃ | Min. insulation resistance constant at 90℃ MΩ.km |
1.5 | 1/1.38 | 0.8 | 12.1 | 36.7 | 0.037 |
2.5 | 1/1.78 | 0.8 | 7.41 | 36.7 | 0.037 |
4 | 1/2.25 | 1.0 | 4.61 | 36.7 | 0.037 |
6 | 1/2.76 | 1.0 | 3.08 | 36.7 | 0.037 |
10 | 7/1.35 | 1.0 | 1.83 | 36.7 | 0.037 |
16 | 7/1.70 | 1.0 | 1.15 | 36.7 | 0.037 |
25 | 7/2.14 | 1.2 | 0.727 | 36.7 | 0.037 |
35 | 7/2.52 | 1.2 | 0.524 | 36.7 | 0.037 |
50 | 19/1.78 | 1.4 | 0.387 | 36.7 | 0.037 |
70 | 19/2.14 | 1.4 | 0.268 | 36.7 | 0.037 |
95 | 19/2.52 | 1.6 | 0.193 | 36.7 | 0.037 |
120 | 37/2.03 | 1.6 | 0.153 | 36.7 | 0.037 |
150 | 37/2.25 | 1.8 | 0.124 | 36.7 | 0.037 |
185 | 37/2.52 | 2.0 | 0.0991 | 36.7 | 0.037 |
Cable operation condition
In air
6.1 The single-core cables are parallel laid, the distance between the cable center is 2 times of the cable diameter for cross-section area of conductor≤185185mm2 and 90mm for cross-sectional area of conductor≥240mm2.
6.1 Ambient air temperature: 40℃.
6.1 Max. continuous operating temperature of conductor: 70℃.
6.2 Direct in the ground
6. The single-core cables are installed separately, the distance between the cable center is 2 times of the cable diameter.
6.1 Soil temperature: 25℃.
6.2 Max. continuous operating temperature of conductor: 70℃.
6.2 Thermal receptivity of soil: 1.0℃.m/W.
6.2 Depth of laying: 0.7m.