PVC Insulated and Sheathed Shipboard Power Cable of Rated

Loading Port:Shanghai

Payment Terms:TT or LC

Min Order Qty:100 m

Supply Capability:30000 m/month

Product Description:

PVC Insulated and Sheathed Shipboard Power Cable of Rated

 

 Product Introduction

The PVC insulated and sheathed shipboard power cable with rated voltage up to and including 0.6/1kV applicable for all kinds of shipboards and over-water buildings like petrol platform at sea.

 

Operating Characteristics:

Rated voltage of cable:0.6/1kV.
Continuous permissible operating temperature:  60℃.
Min bending radius under installation:
Metal braid armored type:6D;
Non-armored type:4D≤25
6D>25


 

Specification: 

Nominal cross-sectional area   mm²

Referenced current carrying capacity

5

7

10

12

14

16

19

24

27

30

33

37

1.5

7

6

5

5

5

5

4

4

4

4

4

3

2.5

10

9

8

7

7

7

6

6

5

5

5

5

Temperature for continues operating

60℃

Surrounding temperature

45℃

Correction Factors at Different Ambient air Temperatures:


The highest permission temperature of conductor

Correction factors at different ambient air temperatures

35℃

40℃

45℃

50℃

55℃

60℃

65℃

70℃

75℃

80℃

85℃

60℃

1.29

1.15

1.0

0.82

65℃

1.22

1.12

1.0

0.87

0.71

70℃

1.18

1.10

1.0

0.89

0.77

0.63

75℃

1.15

1.08

1.0

0.91

0.82

0.71

0.58

80℃

1.13

1.07

1.0

0.93

0.85

0.76

0.65

0.53

85℃

1.12

1.06

1.0

0.94

0.87

0.79

0.71

0.61

0.50

Picture 

 PVC Insulated and Sheathed Shipboard Power Cable of Rated