Power Cables XLPE cable with alternating-current rated voltage of 0.6/1KV

Loading Port:Shanghai

Payment Terms:TT OR LC

Min Order Qty:100 m

Supply Capability:100000 m/month

Product Description:

Electric cable is adopted in transmission and distribution system of electricity.The XLPE cable with alternating-current rated voltage of 0.6/1KV and the cross-link XLPE cable of 35KV and below produced by us not only perform well up to the standards of GB12706,IEC60502 and IEC60840,but also have formed a series,ie.cables of flame-retardant model,refractory model,forts-proof model and water-proof model.

    The technique of oxide-blanket insulation has been successfully applied to the flame-retardant series.Not only have XLPE cable of 0.6/1KV and cross-link XLPE flame-retardant cable reached class A of GB/T12666.5 Test on bunched wires or cable,cross-link flame-retardant XLPE cable with rated voltage of 6/10KV and 8.7/15KV has also reached Class A highly flame-retardant qualification with a margin.On the basis of the cross-link flame-retardant XLPE series,we have developed the low-smoke non-halogen highly flame-retardant oxygen-tight electric cable,the low-smoke non-halogen degree of which conforms to the national standard of GB/T17651.1.2 and GB/T17650.1.2.In general, the cross-link flame-retardant XLPE electric cable produced by us has been in the leading position domestically.

    The refractory-modle cable produced by our factory is the copper-cored cable with the rated voltage of 0.6/1KV,low-smoke non-halogen refractory cable and highly flame-retardant cable,the flame-retardant performance of which is in conformity to GB/T12666.6 Test on fire resisting characteristics of wire or cable,so ,generally the electric cable of refractory series performs well.

     The water-proof cable conforms to the standards of IEC502-2.

1. DC resistance of conductor


Nominal cross-sectional area
(mm2)

Max DC,resistance of conductor at 20℃

Nominal cross-sectional area
(mm2)

Max DC,resistance of conductor at 20℃

Nominal cross-sectional area
(mm2)

Max DC,resistance of conductor at 20℃

Cu

Al

Cu

Al

Cu

Al

1.5

12.1

--

35

0.524

0.868

240

0.0754

0.125

2.5

7.41

12.1

50

0.387

1.641

300

0.0601

0.100

4

4.61

74.1

70

0.268

0.443

400

0.0470

0.0788

6

3.08

4.61

95

0.193

0.320

500

0.0366

0.0605

10

1.83

3.08

120

0.153

0.253

630

0.0283

0.0469

16

1.15

1.91

150

0.124

0.206

800

0.0221

0.0367

25

0.727

1.20

185

0.0991

0.164

1000

0.0176

0.0291