Rated voltage 1kV(1.2kV)and3kV(3.6kV)
PVC insulated Flame retardant and Fire resistant cables
XLPE insulated Flame retardant and Fire resistant cables
Brief introduction
PVC insulated Flame retardant and Fire resistant Power cables are fixed laid in the circuit with frequency 50Hz and voltage upto 3.6/6kV.
XLPE insulated Flame retardant and Fire resistant Power cables are fixed laid in the circuit with frequency 50Hz and voltage upto 3.6/6kV.
We can produce Flame retardant and Fire resistant with PVC or XLPE insulated power cables according to standard GB/T19666,Grade A, B,C or D.
Rated Voltage :0..6/6kV、3.6/6kV。
Conductor of cables can be Copper and Aluminum.The cables can be single core,two cores,three cores,four cores(including three main cores and neutral).five cores (including three main cores and neutral and one earthing core,Four main cores and one neutral).The cables can be with armour and without armour.
We can produce cables with PVC outer sheath,Flame retardant PVC outer sheath or with fire resistant insulation.The cables are produced according to GB/T12706(eqvIEC60502) and GB/T18380-2001(eqv IEC60332),or GB/T19216(IEC60311) and or the BS,DIN, or other international standards. And we also design and produce cables according to the requirement of our clients
Application
1、 Long term working temperature for the cable with PVC insulated is 70℃;
Long term working temperature for the cable with XLPE insulated is 90℃
2、 Short circuit temperature
For PVC insulated cable ,the highest conductor temperature is not more than160℃.(lasting time not over 5 seconds)。
For XLPE insulated cable ,the highest conductor temperature is not more than250℃.(lasting time not over 5 seconds).
3、 Laying temperature not less than 0℃ and the drop height is out of consideration。
4、 The cable with chemical stability,anti acid,anti alkali, anti oil,anti organic solvent,not easy to be burning。
5、 Easy for installation,easy bending and light
6、 Bending ratio:
Item | Single core | Three cores | ||
Non armour | With armour | Non armour | With armour | |
Min bending ratius during installation | 20D | 15D | 15D | 12D |
Near joint box or cable terminal,bending with care and use templet | 15D | 12D | 12D | 10D |
Note:D is the diameter of cable |
Rated voltage 6kV(Um=7.2) and 35kV(Um=40.5)
XLPE insulated power cable
Product standard
XLPE insulated cable has good electrical and pysical properties, resistant to aging, resistant to the environment stress and chemical corrosion operation, with the characteristics of simple structure, easy to use, no drop-height restricton when laying,higher long-term working temerature (90℃).
Table of the voltage,cores and cross-section
Item | Category A 、B | 3.6/6kV | 6/10kV | 8.7/15kV | 12/20kV | 18/30kV | 21/35kV |
Category A 、B | 6/6kV | 8.7/10kV | 12/15kV | 18/20kV | - | 26/35kV | |
Single core | mm2 | 25-1200 | 25-1200 | 35-1200 | 50-1200 | 50-1200 | 50-1200 |
Three core | mm2 | 25-400 | 25-400 | 35-400 | 50-400 | 50-400 | 50-400 |
The cable with Category A rated voltage is used in the situation requiring not over 1 min.of grounding fault lasting time.For the cable with Category B rated voltage, the grounding fault lasting time normally is not over 1 hour, max. lasting time is not over 8 hours, annual ground fault lasting time altogether should not be over 125 hours, Category C includes all the system expect Category A and B.