Detailed Product Description
Al conductor
PE insulated
for laying indoor and outdoor
cheap
Standard compiled with:
GB/T12706-2002 Power cables with extruded insulation and their accessories for rated voltage from 1KV (Um =1.2KV) up to 35KV (Um =40.5KV)
IEC60502-1997 Power cable with extruded insulation and their accessories for rated voltage from 1KV up to 30KV
Service performance
Operating temperature:
Max permissible continuous operating temperature of conductors: 70°C.
Short circuit temperature of conductor:
Max short circuit temperature: 160°C. (less than 5 second)
Laying temperature:
The laying temperature is less than 0°C.
Laying condition and its parameters when current capacity of cables is calculated:
Method of laying | Basic ambient temperature | Soil thermal resistivity |
In air | 40°C | --- |
Direct burial | 25°C | 1°C·M/W |
Layout of cables:
Single core cables: In parallel (spacing side by side=1D D-0verall diameter)
Multi-core cables: laid individually