Online UPS 1-3KVA

Loading Port:Shekou

Payment Terms:TT OR LC

Min Order Qty:-

Supply Capability:-

Product Description:

Online UPS 1-3KVA

XPC 1-3KVA series UPS is an economical, full featured UPS that delivers cost-effective power protection in a compact package. It adopts advanced MCU technology, delivers high reliability and performance, and has intelligent battery management system. XPC 1-3KVA series UPS is best enterprise-class choice for crucial load.

Green and Save Energy
IGBT rectifier offers an input power factor more than 0.99, input THD less than 3%. Therefore it does not pollute the input utility
supply or other devices which share the same utility source.

High Reliability
Wide Input voltage window and auto detection of input frequency function adaptive to adverse utility power grid enviroment.
Extra wige range of input voltage and frequency is suitable for low quality power grid environment 。Complete fault protection
functions, overload, short circuit, overvoltage, under voltage, over temperature protections.Strong overload capability: 5min for 130% rated load and 60s for 150% rated load Intelligent battery management charging/discharging interval time and keep battery long life.

User Friendly Display and Communication
The LED mimic diagram gives clear indication of real-time status and power flow through the UPS.The large LCD graphical display provides an array of performance parameters, fault information and 220historical event log that are useful for troubleshooting.
The system provides RS232 signals for remote monitoring, and SNMP (optional) for web-based monitoring.

Friendly LED display (standard) or LCD display (optional)
Four kinds of optional cards to provide network communication functions (support dry contact, RS232, RS485 and TCP/IP
communication protocols)
Ideally Suited For:
Professional workstations
Small routers and bridges
Point-of-sale terminals
Other sensitive electronics


MODELXPC 1101XPC 1101LXPC 1102XPC 1102LXPC 1103XPC 1103L
Rated Power1KVA/800W2KVA/1600W3KVA/2400W
INPUT
PhaseL+N
Input Voltage(110±5 to 296±5)VAC
Input Frequency(45±0.5 to 55±0.5)Hz
Input PF>0.98
Bypass voltage(80±5 to 286±5)VAC
OUTPUT
Output Voltage220VAC(1±2%)
Output Power Factor0.8
Output Frenqency45Hz55Hz, same with utility power; <45Hz and >55Hz, lock 50Hz
Battery mode
50/60(1±0.2)Hz
THDTHD<3% (linear load)THD<5% (Non-linear)
Transfer TimeNormal to battery mode: 0ms
Between Battery modeand normal mode: <4ms
Overload Capability105±5%Load150±5%30s to bypass;
>150±5%
300ms to bypass;
BATTERY
Battery Voltage36Vdc72Vdc96Vdc
Battery Type7AH/12V× 3pcs7AH/12V× 6pcs7AH/12V× 8pcs
Backup Time (Full Load)>5min(depends on battery capacity for L type)
Charging Current1A/3A4A5A6A7A setable(L type)
SYSTEM
Efficiency>92%
CommunicationRS-232 + Intelligent Slot
RestartAfter turing off due to cut off voltage of battery, UPS will restart
when voltage is in (170±5~286±5Vac) and freqency is in (46~54Hz).
Noise (1m front)<45dBA<50dBA
Operation Temperature0°C to 40°C
Humidity095% non-condensing
Storage Temperature-40°C to 50°C
Altitude<1000m>1000m derated1% per 100m
Dimension(W*D*H)mm145x360x210195x455x330
Weight(kg)126.527163316