Loading Port:China Main Port
Payment Terms:TT OR LC
Min Order Qty:-
Supply Capability:-
Oil-immersed series reactor
1. Purpose
Seriesreactor is mainly used in compensator with parallel, in series with shuntcapacitor , limited the inrush current of switch on during switching capacitor,check the distortion of voltage waveform, remove damage to capacitor ofharmonic and impulse current. In some network and electrical equipment,connected with series reactor as a current-limiting protection, in order tolimit sudden change of the current.
2. Characteristics
(1) No electromagnetic,no pollution: the reactor is derived from iron core for magnetic circuit, withthe cover for magnetic field shield; there is no electromagnetic pollution onthe environment
(2) Low losses,obvious energy-saving effects, eliminated maintenance.
(3) Small in size,fine appearance
3. Voltage grade:6KV~35KV
4. Using condition
(1)Normal service condition
Installation location: outdoors
Altitude:≤1000m
Ambient temperature : -25℃~+40℃
(2)Special condition:can be designed and manufactured as therequirements of the user
5. Code explanation
6. Major performance parameter
System parameter of Oil-immersed series reactor of 10KV
Insulation level: L1 75/AC35KV ; Insulation heat resistant grade : A
Code | Capacity of shunt capacitor set (kvra) | Rated voltage of capacitor (kv) | Rated capacity (kvra) | Rated reactance ratio (%) | Rated current (A) | Rated terminal voltage (v) | External dimension(mm) L1 xL2 x H | Installation dimension(mm) AxB | Total weight(kg) |
CKSQ-72/10-6 | 1200 | 11/√3 | 72 | 6 | 63 | 381 | 1050x650x1250 | 500x500 | 600 |
CKSQ-10810-6 | 1800 | 11/√3 | 108 | 6 | 94.5 | 381 | 1130x730x1500 | 500x500 | 790 |
CKSQ-144/10-6 | 2400 | 11/√3 | 144 | 6 | 126 | 381 | 1230x760x1500 | 550x550 | 1000 |
CKSQ-180/10-6 | 3000 | 11/√3 | 180 | 6 | 157.5 | 381 | 1310x810x1540 | 550x550 | 1180 |
CKSQ-216/10-6 | 3600 | 11/√3 | 216 | 6 | 189 | 381 | 1370x840x1620 | 550x550 | 1320 |
CKSQ-240/10-6 | 4000 | 11/√3 | 240 | 6 | 210 | 381 | 1410x850x1670 | 660x600 | 1450 |
CKSQ-288/10-6 | 4800 | 11/√3 | 288 | 6 | 252 | 381 | 1470x920x1750 | 660x660 | 1700 |
CKSQ-300/10-6 | 5000 | 11/√3 | 300 | 6 | 262.5 | 381 | 1500x940x1800 | 660x660 | 1720 |
CKSQ-360/10-6 | 6000 | 11/√3 | 360 | 6 | 315 | 381 | 1560x980x1850 | 660x820 | 1980 |
CKSQ-480/10-6 | 8000 | 11/√3 | 480 | 6 | 420 | 381 | 1700x1050x1980 | 660x820 | 2445 |
CKSQ-600/10-6 | 1000 | 11/√3 | 600 | 6 | 525 | 381 | 1780x1100x2100 | 660x820 | 2900 |
7. System parameters of Oil-immersed series reactor of 35KV
Insulation level: L1 200/AC85KV or LI 170/AC75KV
Insulation heat resistant grade:A
Code | Capacity of shunt capacitor set (kvra) | Rated voltage of capacitor (kv) | Rated capacity (kvra) | Rated reactance ratio (%) | Rated current (A) | Rated terminal voltage (v) | External dimension(mm) L1 xL2 x H | Installation dimension(mm) AxB | Total weight (kg) |
CKSQ-300/35-6 | 5000 | 11x2 | 300 | 6 | 75.8 | 1320 | 1830x1100x2150 | 820x820 | 2210 |
CKSQ-600/35-12 | 12x2 | 600 | 12 | 69.5 | 2880 | 2170x1320x2540 | 820x820 | 3650 | |
CKSQ-360/35-6 | 6000 | 11x2 | 360 | 6 | 91 | 1320 | 1920x1200x2300 | 820x820 | 2520 |
CKSQ-720/35-12 | 12x2 | 720 | 12 | 83.4 | 2880 | 2310x1430x2700 | 820x820 | 4350 | |
CKSQ-480/35-6 | 8000 | 11x2 | 480 | 6 | 121.3 | 1320 | 2100x1330x2450 | 820x820 | 3180 |
CKSQ-960/35-12 | 12x2 | 960 | 12 | 111.2 | 2880 | 2500x1550x2920 | 1070x1070 | 5250 | |
CKSQ-600/35-6 | 10000 | 11x2 | 600 | 6 | 151.6 | 1320 | 2230x1400x2550 | 820x820 | 3760 |
CKSQ-1200/35-12 | 12x2 | 1200 | 12 | 138.9 | 2880 | 2650x1400x2550 | 1070x1070 | 6280 | |
CKSQ-720/35-6 | 1200 | 11x2 | 720 | 6 | 181.9 | 1320 | 2350x1450x2710 | 820x820 | 4310 |
CKSQ-1400/35-12 | 12x2 | 1440 | 12 | 166.7 | 2880 | 2780x1750x3240 | 1070x1070 | 7150 |
8. Outline and installation dimension
10kV oil immersed series reactor
9. Basic ordering data
l SystemRated voltage and frequency
l capacityof assorted capacitor set
l Rated capacity
l Ratedreactance or reactance ratio
l Rated current
l Other performance data should be indicated in thecontract.