Loading Port:China Main Port
Payment Terms:TT or LC
Min Order Qty:1PC pc
Supply Capability:10,000 per year pc/month
General Of MV Voltage 3KV 6KV 10KV Frequency Inverter
CNBM high Voltage Variable Frequency Drives are designed to be highly reliable with high-performance, yet easy to use.It can satisfy users' need for changing the speed of fans or pumps,as well as improve the productivity.
The series are compatible with all types of three-phase medium voltage asynchronous motors.
Application Filed Of MV Voltage 3KV 6KV 10KV Frequency Inverter
CMAX- series of medium voltage VFD can usually be applied in these fields:
Power generation: induced draft fans, forced draft fans, condensate exhausting pump, boiler feed water pumps, primary fan, secondary fan, circulating pump, mill fan, slurry pump, mill .
Metals: dusting fans, slurry pump, feeding pump, furnace fans, compressor, mill
Cement: fan, discharge fan, waste gas fan, dust collecting fan, dust removing fan, mill.
Oil & Gas: water injection pump, oil transfer pumps, air compressor.
Mining: Fans, media pump, circulating pump, gas pump, oil separating pump, compressor, lift, mill, conveyer, hoisting machine.
Water: water supply pump, circulating pump.
Technology Data Of MV Voltage 3KV 6KV 10KV Frequency Inverter
3KV series VFD
Model | A03/050~ A03/100
| A03/100~ A03/175
| A03/175 ~A03/220 | A03/220~A03/400 | A03/220~A03/610 |
Capacity(kVA) | 250~630 | 630~900 | 900~1150 | 1150~2000 | 2000~3125 |
Rated output current (A) | 50~100 | 100~175 | 175~220 | 220~400 | 400~610 |
Motor power (kW) | 200~400 | 400~710 | 710~900 | 900~1600 | 1600~2500 |
Input frequency | 45Hz~55Hz | ||||
Rted input voltage | 3000V±10% | ||||
Input power factor | 0.95 (>20%load) | ||||
Efficiency | 0.96 with rated load | ||||
Output frequency | 0.5Hz~120Hz | ||||
Frequency resolution | 0.01Hz | ||||
Overload capacity | 120% 1 min, 150% immediately | ||||
Analogue input | 0~10V/4~20mA | ||||
Analogue output | 0~10V/4~20mA | ||||
Acceleration/deceleration time | 0.1~3000s | ||||
Digital output/input | expanded according to requirement | ||||
Ambience temperature | 0~40℃ | ||||
Storage/transport temperature | -40~70℃ | ||||
Cooling | air cooling | ||||
Ambience humidity | <90% without condensation | ||||
Altitude | <1000 m | ||||
IP class | IP20 | ||||
Size(mm)(W×H×D) | 3300×2480×1200 3900×2480×1200
| 4900×2480×1200 6000×2580×1200
| 6000×2580×1300 | ||
Weight (kg) | 3000 ~5000 | 5000 ~7300 | 7300~9200 |
6KV series VFD
Model | A06/050
| A06/050~ A06/080
| A06/080~ A06/100
| A06/100~ A06/170
| A06/170~ A06/220
| A06/220~ A06/400
| A06/400~ A06/610
|
Capacity(kVA) | ≤500 | 500~800 | 800~1000 | 1000~1750 | 1750~2250 | 2250~4000 | 4000~6250 |
Rated output current (A) | ≤50 | 50~80 | 80~100 | 100~170 | 170~220 | 220~400 | 400~610 |
Motor power (kW) | ≤400 | 400~630 | 630~800 | 800~1400 | 1400~1800 | 1800~3250 | 3250~5000 |
Input frequency | 45Hz~55Hz | ||||||
Rated input voltage | 6000V±10% | ||||||
Power factor | 0.95(>20%load) | ||||||
Efficiency | 0.96with rated load | ||||||
Output frequency | 0.5Hz~120Hz | ||||||
Frequency resolution | 0.01Hz | ||||||
Overload capacity | 120% 1 min, 150% immediately | ||||||
Analogue input | 0~10V/4~20mA | ||||||
Analogue output | 0~10V/4~20mA | ||||||
Acceleration/deceleration time | 0.1~3000s | ||||||
Digital input/output | expanded according to requirement | ||||||
Ambience temperature | 0~40℃ | ||||||
Storage/transport temperature | -40~70℃ | ||||||
Cooling | air cooling | ||||||
Ambience humidity | <90%,without condensation | ||||||
Altitude | <1000m | ||||||
IP class | IP20 | ||||||
Size(mm)(W×H×D) | 3600×2480×1200 | 3900×2480×1200 | 4200×2480×1200 5100×2480×1200
| 5200×2580×1200 | 6600×2580×1300 8700×2780×1400
| ||
Weight (kg) | 3500~4000 | 4000~5000 | 5000~6000 | 6000~8000 | 8000~14000 |
10KV series VFD
Model | A10/080 | A10/080~ A10/150
| A10/150~ A10/210
| A10/210~ A10/400
|
Capacity(kVA) | ≤1250 | 1250~2500 | 2500~3500 | 3500~6250 |
Rated output current (A) | ≤80Rated output current (A) | 80~150 | 150~210 | 210~400 |
Motor power(kW) | ≤1000 | 1000~2000 | 2000~2800 | 2800~5000 |
Input frequency | 45Hz~55Hz | |||
Rated input voltage | 10000V±10% | |||
Power factor | 0.95(>20%load) | |||
Efficiency | 0.96with rated load | |||
Output frequency | 0.5Hz~120Hz | |||
Frequency resolution | 0.01Hz | |||
Overload capacity | 120% 1 min, 150% immediately | |||
Analogue input | 0~10V/4~20mA | |||
Analogue output | 0~10V/4~20mA | |||
Acceleration/deceleration time | 0.1~3000s | |||
Digital input/output | expanded according to requirement | |||
Ambience temperature | 0~40℃ | |||
Storage/transport temperature | -40~70℃ | |||
Cooling | air cooling | |||
Ambience humidity | <90%,without condensation | |||
Altitude | <1000m | |||
IP class | IP20 | |||
Size(mm)(W×H×D) | 4500×2480×1200 | 5700×2480×1200 | 6800×2580×1300 | 10600×2580×1300 |
Weight(kg) | 3500~6000 | 6000~8000 | 8000~15000 | 15000~19000 |