Product Description:

Technical Data
◆Number of poles:1,2,3,4,1+N,3+N
◆Nominal current In(A): 1,2,3,4,6,8,10,13,16,20,25,32,40,50,63
◆Characteristics:
◇B The short-circuit release is to be set up to 3 In through 5 In.It serves especially for protection of circuits with such devices which do not cause any current surges(lights or socket circuits etc.)
◇C The short-circuit release is to be set up to 5 In through 10 In.It serves especially for protection of circuits with such devices which cause some current surges(groups of bulbs, motors etc.)
◇D The short-circuit release is to be set up to 10 In through 20 In. It serves especially for protection of circuits with devices which cause high current surges(transformers,double-pole motors,motors with heavy start etc.)
◆Nominal voltage:
◇1P (single-pole)~230/400V 50/60Hz
◇3P (three-pole)~400V 50/60Hz
◆Rupturing capacity:
◇EN60898-10,000A(nominal short-circuit and operational rupturing capacity)
◆Protection:IP40 for a sole MCB with its design, it protects against a hazardous finger or instrument touch as well as against very small foreign objects; It is without any protection against water leakage (water protection is to be solved with design of the switchboard casing)
◆Ambient temperatue: -5oC to +40oC pursuant to EN60898
◆Gauging temperature:+30oC pursuant to EN60898
◆Max.pre-inserted fuse:100AgG(>10kA)
◆Mechanical lifetime:≤20,000 cycles
◆Electrical lifetime:≤8,000 cycles
◆Fastening:By means of an unique snap mechanism(with arrestment in final positions)the carrying DIN strip EN50022,width 35mm, or even onto the falt surface by means of screws.
◆Removal form the DIN strip:
◇By means of an unique auxiliary snap mechanism, the MCB誷 can be removed even from a row of devices mutually interconnected by a forked or reed rack strip without necessity to dismantle the whole interconnecting strip.
◆Input terminals:
◇Clip terminals(with barrier layer), snap-locked against the worse input of a conductor
◇The input and output can be interchanged
◇They enable more conductors as well as interconnecting strips to be connected
◆Connect ability of conductors (Maximum cross-sections):
◇35mm2 solid conductor
◇25mm2 stranded conductor
◆Terminal protection:IP20
◆Tightening moment for terminals
◇2Nm(combined slotted-head screw)
◆Manufacture standard
◇EN60898,same to IEC 60898
◆Selectivity calss:3
◆Colored levers:
For better distinction among circuits in the switchboards,we supply also miniature circuit breaker with distinction of nominal currents by means of colored levers corresponding to the colors of turn fuses
◇0.2A-1.6A(Black)
◇2A(Pink)
◇4A(Brown)
◇6A(Green)
◇8A(Light green)
◇10A(Red)
◇13A(Sandy)
◇16A(Grey)
◇20A(Blue)
◇25A(Yellow)
◇32A(Purple)
◇40A(Black)
◇50A(White)
◇63A(Copper-colored)
◆Can be delivered also with only black levers
◇1-63(Black)