Input Voltage Ranges Home Inverter 500VA-2000VA

Loading Port:China Main Port

Payment Terms:TT or LC

Min Order Qty:1 Piece pc

Supply Capability:4000 Pieces per Month pc/month

Product Description:

Feature

 

This inverter is a DC-TO-AC inverter with auto line-to-battery transfer and integrated charging system, serving as an extended run UPS, a stand alone power source or an automotive inverter.

 

Inverter supplies power from AC power and DC source. When AC cable is connected to a wall socket, utility power goes to connected equipment(s) and /or charges the battery set via charging system. In UPS mode, Inverter automatically converts battery energy into AC power for backing up the connected devices.

 

· Automatic line-to-battery switchover

 

· Selectable input voltage ranges

 

· High efficient DC-to-AC conversion, minimizing energy loss

 

· Rack tower design for flexible placement

 

· Built-in enhanced charger

 

· Intelligent 2-stage charger control for efficient charging and preventing overcharge

 

· Provides overload protection

 

· Auto restart while AC recovery

 

· Multi-function LED indications and buzzer alarms

Main Technical Data

MODEL 

 

HIG500 

HIG1000 

HIG2000 

Capacity 

VA/W 

500VA/300W 

1000VA/600W 

2000VA/1200W 

Input 

Nominal Voltage 

110V/120VAC or 220/230/240VAC 

Voltage Range 

90-145VAC or 170-280VAC (Narrow Range) 

50-145VAC or 90-280VAC (Wide Range) 

Output 

Voltage 

120VAC or 230VAC 

Voltage regulation (Batt.Mode) 

+10% / -18% 

Frequency 

50Hz or 60hz 

Frequency Regulation (Batt.Mode) 

+ / - 0.1Hz 

Output waveform 

Modified Sine-wave 

Battery & Charger

Charger current 

8Amp+ / -1Amp  

10Amp+ / - 1Amp 

10Amp+ / - 1Amp 

DC Voltage 

12V+ /-0.2V 

12V+ /-0.2V 

24V+ /-0.4V 

Overcharge protection 

14.5V+ / - 0.3V charger stops and fault 

29V+ / - 0.6V charger stops and fault 

Transfer Time 

Typical 

6~8ms Typical 

Efficiency 

AC to AC 

>95% 

DC TO DC 

>80% 

Indicator 

AC Mode

Green lighting 

Battery Mode

Yellow lighting 

Battery Charging Mode 

Green flashing every 2 seconds 

Overload 

Red flashing every 0.5 second 

Fault 

Red lighting 

Audible Alarm

Low Battery at Battery Mode 

Sounding every 2 seconds 

Overload 

Sounding every 0.5 seconds 

Fault 

Continuously sounding 

Protection 

Full Protection

Discharge, overcharge, and overload protection 

Physical

Dimension(D*W*H)mm 

224*255*80 

Net Weight(kgs) 

2.0

2.3

2.5

Environment 

Operating Environment

0-40ºC, 0-90% relative humidity ( non-condensing) 

Noise Level 

Less than 55dB