1. Soft Start
2.Energy Saving
3.No impact
4.Speed Regualtion
Technical of High Voltage 6KV Converter Frequency
SNO | Technical specification | UOM | RXPE |
1 | Rating | KW | 190kW to 52000kW |
2 | Model | RMVC Series | |
3 | Indiviual power cell temp. monitoring | Yes | |
4 | Input Transformer | Dry type,Class-H Insulation | |
5 | Input Power Factor | > 0.95 for peed range 25 to 100 % | |
6 | Technology | Multilevel cascaded based | |
multi-level switching IGBT PWM | |||
7 | Voltage | 3kV/3.3kV/4.16kV/6kV/6.6kV/7.2kV/10kV/11kV/13.8kV/33kV/34.5kV | |
8 | Voltage tolerance | ±10% | |
9 | Under voltage dip | -35% 30 sec | |
10 | Input Frequency | 50Hz/60Hz | |
11 | Input Frequency tolerance | Hz | ±5% |
12 | Output Frequency | Max to 200Hz | |
13 | Rectifier device | Diode/IGBT/IEGT | |
14 | Inverter device | IGBT-H bridge/IEGT | |
15 | DC link capacitors | Thin Film Capacitor | |
16 | Variable speed drive efficiency (Including transformer) % | >97% | |
17 | Voltage cut ride through | duration 5 cycles | |
18 | HMI | Window base for all operation+ | |
19 | Controller DCS compatible | Yes | |
20 | Cooling | Air cooling/Liquid Cooling | |
21 | Enclosure protection | Max to IP56 | |
22 | Ambient temperature maximum | ºC | 40 |
23 | Humidity (non condensing) | % | <90 |
24 | Altitude (maximum) | m | 1000 |
25 | Noise at 1 meter | dB(A) | <80 |
26 | Control supply | 380/400V±10% AC 3PH 4 Wire 15kVA | |
27 | Over Load Capacity | 120% for 1 min for Normal Duty/Heavy Duty on Request | |
28 | Special requirements customization | Acceptable |