GIS 72.5 -550kV

Loading Port:China Main Port

Payment Terms:TT OR LC

Min Order Qty:-

Supply Capability:-

Product Description:

Specifications

           80% of the power frequency withstand voltage
the leak rate is low
high operating reliability
good safety performance                

Introduction :
Release time :
2012-8-22 Product Description: Product role With 72.5 ~ 550kV GIS Current Transformer, sulfur hexafluoride gas insulation, mainly used in power systems power measurement, current measurement and relay protection.
Product structure

Features
1, insulation stable: 80% of the power frequency withstand voltage under the partial discharge amount not greater than 5pC.
   2, the leak rate is low: annual leakage rate of less than 0.3%, far better than the 1% of the requirements of the GB.
   3, high operating reliability: pressure SF6 gas zero table, safe operation can be a long time.
    4, good safety performance: explosion-proof device with excellent explosion-proof performance.
   5, high precision: measurement up to meet the 0.1 level.
   6 protection: protect the winding core of high permeability and saturation flux density is high (greater than 1.8T).
Technical parameters

Type

L (S) R-72.5

L (S) R-126

LR-220

LR-500

The devices rated voltage, kV

66

110

220

500

The * Device highest voltage, kV

72.5

126

252

550

Rated frequency Hz

50-60

* Short-time power frequency withstand voltage, kV

160

230

460

740

* Lightning impulse voltage, kV

350

550

1050

1675

Partial discharge level (1.2Um / √ 3)

<5pC

* Rated current, A

300-300

300-300

300-4000

600-5000

* Rated secondary current, A

5 or 1.

1

* Accuracy class (subject combinations)

0.2S; 0.2; 0.5S; 0.55P; 10P

* Rated output, VA

15-50

15-50

10-50

10-30

Safety factor, FS

5 or 10

* Accuracy Limit Factor, ALF

10-40

Short-term thermal stability current, kA / s

40/3

40/3

31.5-63 / 3

50-63/3

Rated dynamic current, kA

100

100

80-125

125-160

SF6 rated pressure (20 ° C), Mpa

0.4

A SF6 Buqi pressure (20 ° C), Mpa

0.35

SF6 gas leakage rate,%

<0.3

SF6 moisture content, μL / L

<150