Table 2.3: Technical Parameters of QD200 Series Frequency Inverters
ITEM | SPECIFICATIONS | |
Main Input | Rated voltage and frequency | Single-phase 200V class: 200V-240V,50Hz/60Hz |
3-phase 400V class: 380V-480V , 50Hz/60Hz | ||
Allowable value of change | Voltage: 380V-15% ~ 480V+10%; Frequency: ±15% | |
Main output | Output voltage | Maximum output voltage equals to input voltage |
Output frequency | 0.5 Hz to 400 Hz | |
Overload capacity | 150% of rated output current for 60s, 200% of rated output current for 2s | |
Control performance | Modulation mode | 3-phase PWM, 2-phase PWM |
Control mode | V/f control for constant torque, V/f control for quadratic load, vector control without PG (open loop control),Energy-saving | |
Setting method of run command | Outer terminal, keyboard panel or serial communication | |
Setting method of speed command | Analog setting, keyboard, serial communication, UP/DOWN speed setting from external terminal | |
Speed setting resolution | Keyboard: 0.1 Hz | |
Analog setting: 0.05/50Hz (10bit) | ||
Speed control precision | V/f control:±2% | |
vector control without PG (open loop control): ±0.2% | ||
Speed control range | V/f control 1:40 | |
vector control without PG (open loop control) 1:200 | ||
Acceleration and Deceleration Time | 0-3200.0s | |
switching frequency | 1.5 kHz ~ 12 kHz, according to junction temperature automatically reduce the switching frequency | |
Analog input | Number | 2 ways: AI1、AI2 |
Type | DC voltage or DC current | |
Maximum input range | AI1: 0 to 5VDC, 0 to 10VDC, 0/4 to 20mA DC receivable AI2: 0 to 10VDC or PTC probe input receivable | |
Analog output | Number | 1 way: AO1 |
Type | DC voltage or DC current | |
Maximum input range | Voltage output: 0 to 10V, Current output: 0/4 to 20mA | |
logic input | Number | 0.75kw-11kW:LI1,LI2,LI3,LI4,AI1,AI2 15kW-500kW:LI,LI2,LI3,LI4,LI5,LI6,LI7,LI8,AI1,AI2 note:2 virtual logic input, capable of configuring AI1 and AI2 into logic input port (positive logic or negative logic) |
Type | Source or Sink | |
Maximum input range | 0-24VDC |
ITEM | SPECIFICATIONS | |
logic output | Number | 0.75kW-11kW: pulse signal output (LO-CLO)、relay output 1(T1A、T1B、T1C) 15kW-500kW:pulse signal output(LO-CLO)、relay output 1、2(T1A-T1B-T1C、T2A-T2B-T2C) |
pulse signal output | ||
relay output | RA-RB-RC, including a NO contact and a NC contact Maximum switch capacity: T1A,T1B: 3A at 250VAC, or 4A at 30VDC T2A,T2B: 2A at 250VAC or 30VDC | |
Serial communication interface | RS485 interface supports Modbus protocol. | |
Display | 4-digit LED digital display | For display of frequency setting, output frequency, fault code and parameter setting etc. |
Environment | Standard | Development of VSC200 series frequency inverters follows strict international standards and relevant recommended IEC and EN standards for control devices, especially IEC/EN61800-5-1 and IEC/EN61800-3. |
Altitude | Derating unnecessary when altitude is 1000m or below (Derating necessary at altitude higher than 1000m) | |
Ambient environment | 0.75kW-11kW: Reliable operation at -10 ~ 50°C without derating. When top protective cover is taken off, the environment temperature can be as high as +50 °C. Above +50 °C, the current drops by 2.2% for each rise of 1 °C in temperature. 15kW-500kW: Reliable operation at -10 ~ 40°C without derating. Storage: -25 ~ 70°C | |
Humidity | No condensed water or drip at 5 ~ 95%, In accordance with IEC60068-2-3 | |
Impact strength | 15gn for continuous 11ms, In accordance with IEC/EN60068-2-27 | |
Maximum antipollution capacity | Class 2, in accordance with IEC/EN61800-5-1 | |
Structure | Protection level | Top: IP41 (without removing the protective top cover). Other parts: IP20 |
Cooling Method | Forced Air cooling | |
Installation method | Wall mounted |