Fluoroplastics Insulated Insulated Power Cable

Loading Port:Shanghai

Payment Terms:TT or LC

Min Order Qty:100 m

Supply Capability:100000 m/month

Product Description:

Introduction:
It can be laid in the transmission and distribution circuit under the AC50Hz and the voltage of 0.6/1kv.

Specification:

Type

Name

Temperature

F2H8

PVFD insulated and sheathed power cable

-60℃-150℃

F46H3

Poly HFP insulated and sheathed power cable

-60℃-200℃

F4H4

PTFE insulated and sheathed power cable

-60℃-250℃

 Specifications

Type

No. Of cores

Nominal cross-sectional area mm2

F2H8

1

1.5-240

F46H3

23

1.5-70

F4H4

3+14

4-50

Technical parameters and Features:
1.the polyvinylidene insulated and sheathing power cable has a tensile strength up to 400 kgf/cm2, and is highly wearable.
2. F-propylene-wide insulated and jacket power cable is still interferential at -60 ℃, whose dielectric constant is only 2.0,
Volume resistivity is up to 1018 Ω • cm and Dielectric strength is up to 500 V / min.
3.the  electric performance of Teflon insulated and sheathing power cable is  equivalent to that of F-propylene-wide insulated and sheathing power  cable
      F plastic insulated and sheathing power cable has such  properties as being strongly resistant to chemical corrosion and  climate, waterproof and fire-retardant.



Cable operation condition:Cable operation condition:
6.1In air
6.1 The single-core cables are parallel laid, the distance between the cable center is 2 times of the cable diameter for cross-section area of conductor≤185185mm2 and 90mm for cross-sectional area of conductor≥240mm2.
6.1Ambient air temperature: 40℃.
6.1 Max. continuous operating temperature of conductor: 90℃.
6.2 Direct in the ground
6.1 The single-core cables are installed separately, the distance between the cable center is 2 times of the c ccable diameter.
6.1 Soil temperature: 25℃.
6.2 Max. continuous operating temperature of conductor: 90℃.
6.2 Thermal resistively of soil: 1.0℃.m/W.
6.2 Depth of laying: 0.7m.