Loading Port:China Main Port
Payment Terms:TT OR LC
Min Order Qty:-
Supply Capability:-
Epoxy Cast Resin Dry-type IronCore Shunt Reactor
1. Usage
n To reduce power frequency voltage rise caused by capacitance effect of long distance distribution when no-load or light load;
n To improve voltage distribution alongthe line and reactive power distribution in the light-load line, reduce linelosses and improve power factor;
n To reduce secondaryarc current, accelerate secondary arc extinguishing, and improve success rateof line automatic reclosing;
n To be beneficial for eliminatinggenerator self-excitation;
n To reduce equipment capacity andsave investment.
2. Product Characteristics
l The coilsare covered by glass fiber and vacuum casted by epoxy resin,it has good mechanical performance, high reliability ,high safety andlong working life.
l It has good moisture resistance andcan be operated in high humidity environment.
l Low noise, the core is casted as awhole by epoxy resin and form as a solid body, when it is running only cause littlevibration.
l Thin insulation structure, and theair flue is embedded inside to strengthen the heat dispersion, and the short-circuit overload is strong.
l Flame retardant, explosion proof,no environment pollution.
l Low-loss, significant energysaving, and free maintenance
l Small in size, light in weight, niceappearance
3. Voltage grade:6KV~35KV
4. Using Condition
l Normal serviceconditions
Installation:Indoor
Altitude: ≤1000m
Ambient temperature:-5℃~+40℃
Maximum dailytemperature difference:≤25℃
l Special conditions: can be made customized.
5. Model coding
Connection:
6. Parameters
10kV grade
insulation level: I 75/AC35KV;Insulation heat endurance class:F (triangletype)
No. | Type | Rated capacity kVar | Rated voltage kV | Rated Current A | Rated reactance Ω | Noise dB (A) | Outline dimension mm | Weight kg | |||||
H | L1 | L2 | L3 | L4 | Φ d1 | ||||||||
1 | BKSC-600/10 | 600 | 10 | 166.7 | 166.7 | 66 | 1150 | 820 | 700 | 610 | 760 | 18 | 2000 |
2 | BKSC-800/10 | 800 | 10 | 46.2 | 125 | 68 | 1280 | 1040 | 850 | 740 | 890 | 18 | 2400 |
3 | BKSC-1000/10 | 1000 | 10 | 57.7 | 100 | 70 | 1500 | 1200 | 1100 | 960 | 1120 | 18 | 2900 |
4 | BKSC-1500/10 | 1500 | 10 | 86.6 | 66.67 | 70 | 1600 | 1310 | 1200 | 1050 | 1200 | 18 | 3800 |
5 | BKSC-2000/10 | 2000 | 10 | 115.5 | 50 | 70 | 1780 | 1420 | 1300 | 1130 | 1300 | 18 | 4850 |
6 | BKSC-3000/10 | 3000 | 10 | 173.2 | 33.3 | 70 | 1800 | 1580 | 1450 | 1260 | 1460 | 18 | 6200 |
7 | BKSC-4000/10 | 4000 | 10 | 231 | 25 | 71 | 1880 | 1650 | 1520 | 1320 | 1520 | 18 | 8500 |
8 | BKSC-5000/10 | 5000 | 10 | 289 | 20 | 71 | 1980 | 1800 | 1600 | 1390 | 1610 | 18 | 9100 |
9 | BKSC-6000/10 | 6000 | 10 | 346.4 | 16.7 | 74 | 2100 | 1850 | 1700 | 1480 | 1710 | 18 | 10700 |
10 | BKSC-8000/10 | 8000 | 10 | 461.8 | 12.5 | 75 | 2300 | 2000 | 1850 | 1610 | 1860 | 24 | 13200 |
11 | BKSC-10000/10 | 10000 | 10 | 577.3 | 10 | 76 | 2400 | 2160 | 2000 | 1740 | 2000 | 24 | 16400 |
12 | BKSC-16000/10 | 16000 | 10 | 923.7 | 6.3 | 77 | 2500 | 2210 | 2050 | 1780 | 2080 | 30 | 24000 |
Note:
1) Special product could be available basedon customers' requirement.
2) Reference data only, not for technical specifications.
3) Noise in above forms is sound power level.
35KV grade;insulation level: LI170/AC70KV or LI200/AC85KV;insulation heat endurance class:F (triangletype)
No. | MODEL | Rated capacity kvar | Rated voltage kv | Rated Current A | Rated reactance Ω | Noise dB (A) | Dimensions | Weight (kg) | |||||
H | L1 | L2 | L3 | L4 | Φ d1 | ||||||||
1 | BKSC-3000/35 | 3000 | 35 | 49.5 | 408 | 71 | 1800 | 1800 | 1700 | 1480 | 1610 | 18 | 7800 |
2 | BKSC-4000/35 | 4000 | 35 | 66 | 306 | 71 | 1950 | 1900 | 1800 | 1590 | 1700 | 18 | 9200 |
3 | BKSC-5000/35 | 5000 | 35 | 82.5 | 245 | 72 | 2250 | 2200 | 2080 | 1810 | 1950 | 18 | 10500 |
4 | BKSC-6000/35 | 6000 | 35 | 99 | 204 | 75 | 2600 | 2600 | 2450 | 2130 | 2280 | 18 | 12100 |
5 | BKSC-8000/35 | 8000 | 35 | 132 | 153 | 76 | 2800 | 2800 | 2640 | 2300 | 2450 | 24 | 15000 |
6 | BKSC-10000/35 | 10000 | 35 | 165 | 122.5 | 77 | 3000 | 3000 | 2840 | 1460 | 2620 | 24 | 17800 |
7 | BKSC-12000/35 | 12000 | 35 | 198 | 102 | 77 | 3150 | 3150 | 3000 | 2600 | 2780 | 30 | 20500 |
Note:
1) Special product could be available basedon customers' requirement.
2) Reference data only, not for technical specifications.
3) Noise in above forms is sound power level.
7. Triangle type dimension figure:
10KV grade;insulationlevel: I 75/AC35KV; insulation heat endurance class:F (linetype)
No. | Type | Rated capacity kVar | Rated voltage kV | Rated Current A | Dimensions mm | Weight kg | |||||
H | L1 | L | B | B1 | Φ d1 | ||||||
1 | BKSC-600/10 | 600 | 10 | 166.7 | 1280 | 480 | 1570 | 1200 | 1270 | 18 | 2400 |
2 | BKSC-800/10 | 800 | 10 | 46.2 | 1400 | 550 | 1780 | 1280 | 1350 | 18 | 2800 |
3 | BKSC-1000/10 | 1000 | 10 | 57.7 | 1600 | 550 | 1900 | 1280 | 1350 | 18 | 3300 |
4 | BKSC-1500/10 | 1500 | 10 | 86.6 | 1750 | 660 | 2150 | 1100 | 1150 | 18 | 4200 |
5 | BKSC-2000/10 | 2000 | 10 | 115.5 | 1880 | 750 | 2300 | 1200 | 1250 | 18 | 5350 |
6 | BKSC-3000/10 | 3000 | 10 | 173.2 | 2150 | 750 | 2450 | 1200 | 1250 | 18 | 6700 |
7 | BKSC-4000/10 | 4000 | 10 | 231 | 2270 | 820 | 2580 | 1250 | 1300 | 18 | 9000 |
8 | BKSC-5000/10 | 5000 | 10 | 289 | 2380 | 820 | 2680 | 1250 | 1300 | 18 | 9600 |
9 | BKSC-6000/10 | 6000 | 10 | 346.4 | 2500 | 900 | 2850 | 1300 | 1350 | 18 | 11200 |
10 | BKSC-8000/10 | 8000 | 10 | 461.8 | 2620 | 950 | 3000 | 1300 | 1350 | 24 | 13600 |
11 | BKSC-10000/10 | 10000 | 10 | 577.3 | 2860 | 1070 | 3300 | 1350 | 1400 | 24 | 16800 |
12 | BKSC-16000/10 | 16000 | 10 | 923.7 | 3200 | 1150 | 3650 | 1350 | 1400 | 30 | 24800 |
Note:
1) Special product could be available basedon customers' requirement.
2) Reference data only, not for technical specifications.
3) Noise in above forms is sound power level.
35KV grade;insulation level: LI170/AC70KV or LI200/AC85KV;insulation heat endurance class:F (linetype)
No. | MODEL | Rated capacity kvar | Rated voltage kv | Rated Current A | Rated reactanceΩ | Noise dB (A) | Dimensions | Weight (kg) | |||||
H | L1 | L | B | B1 | Φ d1 | ||||||||
1 | BKSC-3000/35 | 3000 | 35 | 49.5 | 408 | 71 | 2200 | 1000 | 3100 | 1100 | 1200 | 18 | 9000 |
2 | BKSC-4000/35 | 4000 | 35 | 66 | 306 | 71 | 2380 | 1050 | 3250 | 1100 | 1200 | 18 | 10500 |
3 | BKSC-5000/35 | 5000 | 35 | 82.5 | 245 | 72 | 2630 | 1100 | 3400 | 1200 | 1300 | 18 | 12100 |
4 | BKSC-6000/35 | 6000 | 35 | 99 | 204 | 75 | 2800 | 1150 | 3550 | 1200 | 1300 | 18 | 13800 |
5 | BKSC-8000/35 | 8000 | 35 | 132 | 153 | 76 | 3020 | 1220 | 3750 | 1320 | 1470 | 24 | 16400 |
6 | BKSC-10000/35 | 10000 | 35 | 165 | 122.5 | 77 | 3200 | 1250 | 3820 | 1320 | 1470 | 24 | 19300 |
7 | BKSC-12000/35 | 12000 | 35 | 198 | 102 | 77 | 3380 | 1300 | 4000 | 1400 | 1550 | 30 | 22000 |
Note:
1) Special product could be available basedon customers' requirement.
2) Reference data only, not for technical specifications.
3) Noise in above forms is sound power level.
8. Line type dimension figure:
9. Basic data for ordering
l Rated capacity;
l Rated voltage;
l Highest working voltage;
l Rated current;
l Rated frequency;
l Other performance data should beindicated in the contract.