Loading Port:China Main Port
Payment Terms:TT or LC
Min Order Qty:1 Unit unit
Supply Capability:100 Units per Month unit/month
Machine parameters:
#Rated voltage (V) 400/230
#Wiring three-phase four-wire
#Power factor 0.8 (lag)
#Cooling System Water cooled
#Highly elastic rubber shock absorbers damping system
#Integrated settlement of purchase
#Steady state voltage regulation rate% ≤ ± 1
#Voltage transient adjustment rate% ≤ ± 20
#Voltage stabilization time S ≤ 1.5
#Voltage fluctuation rate% ≤ ± 0.5
#Current steady-state adjustment rate% ≤ 5
#The current transients adjustment rate% ≤ ± 10
#Current stabilization time S ≤ 5
#Current volatility% ≤ 0.5
#The warranty period is one year or one thousand hours, whichever occurs first. (GB)
The engines of various parameters:
#Model: KTA19-G3A power (KW): 504
#Fuel: diesel Speed mode: Electronic
#Diesel consumption (Liter / hr) 102.85 Oil Capacity (L) 50
#Displacement (L) 19 Speed (m / min) 1500
#Compression ratio 13.9:1 Bore / Stroke: 159/159
#Type: Four-stroke, six-cylinder, in-line cooling method water-cooled
#Start way: electric start Power DV24V
#Intake: exhaust gas turbocharger cold ignition sequence 1-5-3-6-2-4
The alternator parameters
#Model the: HX5FS power (KW): 500
#Excitation mode: brushless excitation frequency (HZ) 50
#Cooling: cooling voltage regulation system: AVR automatic voltage regulator
#Protection class: IP Insulation class: H
#Overload capacity: 1.5IE not less than the a 2min short-time overcurrent: 3 ~ 5 le not less than 5S