Cu or Al conductor, XLPE Insulated, PVC Sheathed Power Cable

Loading Port:China main port

Payment Terms:TT OR LC

Min Order Qty:200 m

Supply Capability:20000 m/month

Product Description:

Specifications

0.6/1KV,11-33KV, Cu or Al conductor, XLPE Insulated, PVC Sheathed Power Cable

Model

 

ModelName
YJV,      YJLVCu or Al conductor, XLPE Insulated, PVC Sheathed Power Cable
YJV22,  YJLV22Cu or Al conductor, XLPE Insulated, steel tape armoured PVC Sheathed Power Cable
YJV32,  YJLV32Cu or Al conductor, XLPE Insulated, steel wire armoured PVC Sheathed Power Cable

 

Production

 

ModelCoresRated Voltage KV
3.6/6

6/6

6/10

8.7/10

8.7/15

12/2018/20
18/30
Nominal cross section area of conductor (mm2)
YJV, YJLV, YJY, YJLY325~63025~63025~50035~50050~400
125~80025~80025~80035~80050~630

YJV22, YJLV22

YJY23, YJLV23

325~63025~63025~50035~50050~400
125~80025~80025~80035~80050~630

YJV32, YJLV32

YJY32, YJLY32

325~63025~63025~40035~40050~240
125~80025~80025~80035~80050~630

Voltage rating for XLPE cable is 0.6/1KV~11/33KV

 

Max.conductor temperature:

 

PVC, PE insulated cable: 70°c

 

XLPE insulated cable: 90°c

 

Max. short-circuit temperature of the conductor should not exceed:

  

PVC insulated cable: 160°c

  

PE insulated cable: 130°c  

 

XLPE insulated aerial cable: 250°c

 

The duration time should not exceed 5 Sec.

 

The ambient temperature under installation: -15°c--45°c

 

The bending radius of a single-core cable should not less than 20 times of the cable diameter

 

The bending radius of a multi-core cable should not less than 15 times of the cable diameter