Product Introduction:
The XLPE insulated shipboard/marine power cable with rated voltage up to and including 0.6/1kV is applicable for all kinds of shipboards and over-water buildings like petrol platform at sea.
Operating Characteristics:
Rated voltage of cable:0.6/1kV.
Continuous permissible operating temperature: 85℃.
Min bending radius under installation
Metal braid armored type:6D;
Non-armored type:4D≤25
6D>25
Specification:
| DC resistance of Conductor | XLPE Insulation resistance ≥ MΩ/km | |
20℃ | 工作温度 | ||
1 | 18.2 | 1077 | 1.077 |
1.5 | 12.2 | 949 | 0.949 |
2.5 | 7.56 | 785 | 0.785 |
4 | 4.70 | 664 | 0.664 |
6 | 3.11 | 567 | 0.567 |
10 | 1.84 | 458 | 0.458 |
16 | 1.16 | 376 | 0.376 |
25 | 0.734 | 385 | 0.385 |
35 | 0.529 | 331 | 0.331 |
50 | 0.391 | 318 | 0.318 |
70 | 0.270 | 294 | 0.294 |
95 | 0.195 | 254 | 0.254 |
120 | 0.154 | 246 | 0.246 |
150 | 0.126 | 258 | 0.258 |
185 | 0.100 | 264 | 0.264 |
240 | 0.0762 | 246 | 0.246 |
300 | 0.0607 | 233 | 0.233 |
| Technical Properties | Type DA | Type SA | Type SNA | Type SC | Type SNC |
1 | D.C. resistance of Conductor(Ω/km) | See above table | ||||
2 | Insulation resistance(Ω/km) | See above table | ||||
3 | Power frequency voltage test for 4h | Insulated and no breakdown at 3.5kV | ||||
4 | XLPE insulation hot set test | ≤175% | ||||
5 | Single vertical burning test | IEC60332-1 | — | |||
6 | Bundled burning test | IEC60332-3(A type) | ||||
7 | Burning smoke density test |
— |
— |
— |
60% | |
8 |
Fire resistance test | No breakdown for 90min at 750℃ | ||||
9 | Burning gas corrosion test | — | — | |||
9.1 | HCL Content (mg/g) | — | — | — | Not more than 5 | |
9.2 | PH value | Not less than 4.3 | ||||
9.3 | Conductibility (μs/mm) | Not more than 10 |