Loading Port:Shanghai
Payment Terms:TT OR LC
Min Order Qty:100 m
Supply Capability:30000 m/month
Product Introduction:
The product applies for A.C supply & distribution system and is manufactured according to State Coal industry standard MT818.13-1999.Long-term service temperature of the cable conductor should not exceed 90℃.Max. temperature of conductor during cutting-out shall not exceed 250℃(max. duration 5S)..
Operating Characteristics:
ØRated Voltage:1.8/3~3.6/6kV
ØMin. Ambient Temperature: -40℃
ØNormal Operating Temperature:90~250℃
ØMin. bending radius is no less than 30 times of cable thickness
Specification:
Type and Description:
| Description |
MYJV | XLPE insulated ,PVC sheathed power cable for coal mine |
MYJV22 | XLPE insulated , steel tape armored , PVC sheathed power cable for coal mine |
MYJV32 | XLPE insulated , fine steel wire armored, PVC sheathed power cable for coal mine |
MYJV42 | XLPE insulated , heavy steel wire armored, PVC sheathed power cable for coal mine |
Cable Specifications:
Type | Cores | Rated Voltage kV | |||
0.6/1 | 1.8/3 | 3.6/6 6/6 | 6/10 8.7/10 | ||
Nominal cross-section mm² | |||||
MYJV | 3 | 1.5~300 | 10~300 | 25~300 | 25~300 |
MYJV22 | 3 | 4~300 | 10~300 | 25~300 | 25~300 |
MYJV32 | 3 | 4~300 | 10~300 | 25~300 | 25~300 |
MYJV42 | 3 | 4~300 | 10~300 | 25~300 | 25~300 |
Nominal Thickness of Insulation:
Nominal cross sectional area of conductor | Rated Voltage kV | ||||
0.6/1 | 1.8/3 | 3.6/6 | 6/6 6/10 | 8.7/10 | |
| |||||
1.5 | 0.7 | — | — | — | — |
2.5 | 0.7 | — | — | — | — |
4 | 0.7 | — | — | — | — |
6 | 0.7 | — | — | — | — |
10 | 0.7 | 2.0 | 2.5 | 3.4 | — |
16 | 0.7 | 2.0 | 2.5 | 3.4 | 4.5 |
25 | 0.9 | 2.0 | 2.5 | 3.4 | 4.5 |
35 | 0.9 | 2.0 | 2.5 | 3.4 | 4.5 |
50 | 1.0 | 2.0 | 2.5 | 3.4 | 4.5 |
70 | 1.1 | 2.0 | 2.5 | 3.4 | 4.5 |
95 | 1.1 | 2.0 | 2.5 | 3.4 | 4.5 |
120 | 1.2 | 2.0 | 2.5 | 3.4 | 4.5 |
150 | 1.4 | 2.0 | 2.5 | 3.4 | 4.5 |
185 | 1.6 | 2.0 | 2.5 | 3.4 | 4.5 |
240 | 1.7 | 2.0 | 2.6 | 3.4 | 4.5 |
300 | 1.8 | 2.0 | 2.8 | 3.4 | 4.5 |