Computer instrumental cable automatic control system

Loading Port:Shanghai

Payment Terms:TT OR LC

Min Order Qty:100 m

Supply Capability:100000 m/month

Product Description:

It is  used in the automatic control system which the computer is as the main  equipment, suitable for DAS in the industrial control system, MCM,SCM and DCS in  the alarm system. It can connect all kinds of the transducer, transmit the  analog and digital signal of the testing, controlling, interlocking and alarm in  the prodction.

PE or  flame-retardant PE is used as the insulation.When transmitting the signal with  low frequency, short distance or without any special requirements,PVC insulation  can be used.If used in the special site, it should be used the following  insulation, such as EPR, low-smoke and halogen-free polyolefin, PP or silicon  rubber, fluoroplastic.In the table of structure size and prodcut weight, the  reference of the sub shielded, general shielded, sub plus general shielded for  pairs and triple are shown.We can provide the data according to the special  needs.

Implemented standard

British standard BS5308,enterprise  standard

Chracteristics

1)       Rated AC Voltage:  U0/U:300/500V

2)       The highest operating  temperature of condcutor:

PE  insulation--70;      XLPE insulation,EPR--90;           Silicon  rubber,fluoroplastic--200;                               low smoke and  halogen-free polyolefin--70;                     low-smoke and halogen-free  Cross-linked polyolefin-90 and  105 two  types.

3)       The lowest environment  temperature:


Item

The  lowest environment tem

Installation and laying tem

Fixed  deploy

None  fixed

Constant tem cable

-40

-15

≥0

Fluoroplastic and silicon rubber  cable

-60

-20

≥-25

4)       Allowable minimum bending  radius:

No  armor,inerlocked or braided armor nosmaller than 6times of the outer diameter of  the cable

Copper tape shielded or steel wire an steel tape wrapped armor: no  smaller than 12times of the outer diameter of the  cable.