Centre Rotating Double Break isolating switch

Loading Port:Qingdao

Payment Terms:TT OR LC

Min Order Qty:1 unit

Supply Capability:400 unit/month

Product Description:

Product Classification and Main Technical Specification

 

1), product classification

 

Voltage level: 126kV, 145kV, 170kV, 252kV, 363kV, 420kV, 550kV.

 

Current level: 2000A, 3150A, 4000A, 5000A

 

Auxiliary earthing switch type: None earthing switch, left earthing switch, right earthing switch, double earthing switch.

 

2), Main Technical Specifications

Technical Specifications
GW7-126GW7-145GW7-170
Rated voltage kV
126145170
The rated current A
2000, 3150, 40002000, 3150, 4000, 5000
DisconnectorRated peak withstand current kA125125,160
Rated short-time withstand current (RMS)kA505050,63
Rated short circuit duration s333
Grounding switchRated peak withstand current kA125125125,160
Rated short-time withstand current (RMS)kA505050,63
Rated short circuit duration s333
Rated short-time power frequency withstand voltage (RMS) kVto earth230275325
across isolating point230+70315375
Rated lightning impulse withstand voltage (peak) kVto earth550650750
across isolating point550+100750860
open and close busbar for current transferopen and close current A250025002500
transfer voltage V400400400
open and close times100100100
open and close low currentcapacitance current A112
inductance current A 0.50.51
Radio interference level
less than 500 μv
Mechanical life 
300030003000
rated terminal static mechanic load Nlongitudinal level125015001500
Horizontal level75010001000
Vertical force10012501250
rated contact area mmLongitudinal displacement350350350
horizontal displacement350350350
Vertical displacement300300300
All applied in an altitude of 2000m 

 

Technical Specifications
GW7-252GW7-363GW7-420GW7-550
Rated voltage kV
252363420550
The rated current A
2000, 3150, 4000, 50002000, 3150, 4000, 50003150, 4000,5000
DisconnectorRated peak withstand current kA125, 160125, 160125, 160125, 160
Rated short-time withstand current (RMS)kA50, 6350, 6350, 6350, 63
Rated short circuit duration s3333
Grounding switchRated peak withstand current kA125, 160125, 160125, 160125, 160
Rated short-time withstand current (RMS)kA50, 6350, 6350, 6350, 63
Rated short circuit duration s3333
Rated short-time power frequency withstand voltage (RMS) kVto earth460510520740
across isolating point460+145510+210610740+315
Rated lightning impulse withstand voltage (peak) kVto earth1050117514251675
across isolating point1050+2001175+2951425+2401675+450
Rated operation impulse withstand voltage(peak) kVto earthnone95010501300
across isolating pointnone850+295900+3451175+450
open and close busbar for current transferopen and close current A2500
transfer voltage V427
open and close times100
open and close low currentcapacitance current A2
inductance current A 1
Radio interference level
less than 500 μv
Mechanical life 
3000
rated terminal static mechanic load Nlongitudinal level2000250040004000
Horizontal level1500200020002000
Vertical force1250150020002000
rated contact area mmLongitudinal displacement500500600600
horizontal displacement500500600600
Vertical displacement450450500500
All applied in an altitude of 2000m