APPLICATIONS suitable for use as follows: |
Joysense Type RHH or RHW-2 OR USE-2 conductors are used with conduit as specified in the NEC®1. May also be used as underground service entrance cable, for direct burial, at conductor temperatures not to exceed 90℃. When used as RHW-2 or USE-2 conductor temperatures shall not exceed 90℃ in wet or dry locations. Voltage rating for RHH or RHW-2 or USE-2 conductors is 60V. |
STANDARDS&FEFERENCES |
Joysense Type RHH or RHW-2 or USE-2 conductors meet or exceed UL Standard 44 (for RHH or RHW-2), UL Standard 854(for USE-2), Federal Specification A-A-59544, and requirements of the NEC®. |
CONSTRUCTION |
Joysense Type RHH or RHW-2 or USE-2 aluminum conductors are AA-8000 seriesAluminum Alloy, compact stranded. Insulation is an abrasion, moisture, heat, and sunlight resistant black cross-linked polyethylene (XLP). |
SPECIFICATIONS |
Conductors shall be UL-listed Type RHH or RHW-2 or USE-2, suitable for operation at 600 V or less in wet or dry locations, including direct burial in the earth. Conductors shall be Aluminum Alloy, XLP insulated, as manufactured by Joysense Company. |
WEIGHTS,MEASUREMENTS AND PACKAGING | |||||||
CONDUCTOR SIZE (AWG or kcmil) | INSULATION THICKNESS (mils) | NOMINAL O.D.(mils) | AMPACITIES*(AMPS) | APPROXIMATE NET WEIGHT PER 1000ft(lbs) | STANDARD PACKAGE | ||
60℃ | 75℃ | 90℃ | |||||
8 | 60 | 257 | 30 | 40 | 45 | 36 | B |
6 | 60 | 292 | 40 | 50 | 60 | 49 | B |
4 | 60 | 336 | 55 | 65 | 75 | 65 | B |
2 | 60 | 391 | 75 | 90 | 100 | 94 | B |
1 | 80 | 462 | 85 | 100 | 115 | 126 | B |
1/0 | 80 | 499 | 100 | 120 | 135 | 151 | B |
2/0 | 80 | 539 | 115 | 135 | 150 | 182 | B |
3/0 | 80 | 586 | 130 | 155 | 175 | 221 | B |
4/0 | 80 | 638 | 150 | 180 | 205 | 269 | B |
250 | 95 | 713 | 170 | 205 | 230 | 326 | B |
300 | 95 | 763 | 190 | 230 | 255 | 381 | B |
350 | 95 | 809 | 210 | 250 | 280 | 435 | B |
400 | 95 | 852 | 225 | 270 | 305 | 488 | B |
500 | 95 | 929 | 260 | 310 | 350 | 595 | B |
700 | 110 | 1100 | 310 | 375 | 420 | 829 | C |
750 | 110 | 1131 | 320 | 385 | 435 | 881 | C |
1000 | 110 | 1283 | 375 | 445 | 500 | 1145 | C |
FAQ Allowable Ampacites: 60℃-When terminated to equipment for circuits rated 100 amperes or less or marked for 14 through 1 AWG conductors. 75℃-When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG. Dweling –For units. Condutors shall be permitted at listed ampacitees as 120/240 volt, 3-wire, single-phase services and feeders. All conductors are compact stranded construction comdlying with UL standard 44. |