FEATURES
Rated voltage U(Um) is 10(12) kilovolts or 35(42) kilovolts. It applies to the system of the duration of single phase earthing fault normally less than 1 minutes each time or the system of maximum duration less than 8 hours each time, but the total duration not more than 125 hour.
Ambient temperature should be not lower than -20°C when cable is installed.
Maximum temperature is 250°C When cable is shorted for less than 5 seconds for XLPE insulated cable.
Minimum bending radius is as follows when cable is installed:
1.for single—core cable—20(D+d),
unit: millimeter
2.for multi—core cable—15(D+d),
unit: millimeter
Note: D denotes the overall diameter of cable, while d means the diameter of the conductor, unit: millimeter.