Loading Port:Shanghai
Payment Terms:TT OR LC
Min Order Qty:1 pc
Supply Capability:8000 pc/month
Product Description
Production Introduction:
This series inverter for double transformation power supply system.When the power grid appear outage, voltage instability, voltage interference, surge, peak and mains noise and other bad phenomenon, can guarantee the load working normally.Application:
Widely used in electric power, communication, radio and television, banking, taxation and IT industry etc. To provide quality stable power for equipment load.
Working principle:
1. normal operation
Battery through the isolation diode to inverter power supply, and then by inverter transformation into stable alternating current (ac), Through static switch switch to EMI output filter for filtering, Finally on the output side also get a pure stable power supply to the load. From the inverter fault to the mains supply the entire process output no intermittent time. At the same time, the mains through another branch supply to charger after transformation to the battery charging. Showen as below:
2. Automatic bypass operation
When in the following situations inverter will automatically switch to bypass state power supply:
1)The front panel "ON/OFF" button switch without press the trigger boot, or after trigger not go by 20 seconds testing time delay.
2) Standby state
3) Inverter output overload or battery low voltage
4) inverter circuit built-in malfunction
When there is above circumstance, after the input mains through the filter, is no longer through the inverter switching, but directly to the static switch, after switch to the filter and then filter output. In the bypass state, mains also can charge for the battery.
Technical parameters
(1)Single into single out technical parameters
1KL~20KL(Single into single out model) technology parameter list | |||||||
Model | 1KL | 2kL | 3KL | 6KL | 10KL | 15KL | 20KL |
Rated capacity(KW) | 1KAV | 2KAV | 3KAV | 6KAV | 10KAV | 15KAV | 20KAV |
Input voltage | Single phase two line + ground line, 220V±25% | ||||||
Battery voltage | 48VDC | 96/192VDC | 192/240VDC | ||||
noise | ≤52dB(Distance 1m) | ≤60dB(Distance 1m) | |||||
size (W*D*Hmm) | 256×618×626 | 370×690×763 | |||||
Weight(kg) | 30 | 40 | 45 | 60 | 105 | 130 | 160 |
(2) three into single out technical parameters
RLD6KL~60KL(three into single out model) technology parameter list | ||||||||
Model | 10KL | 15kL | 20KL | 30KL | 40KL | 50KL | 60KL | |
Rated capacity(KW) | 10KAV | 15KAV | 20KAV | 30KAV | 40KAV | 50KAV | 60KAV | |
Input voltage | three phase four line + ground line, 3800V±25% | |||||||
Battery voltage | 384VDC | |||||||
noise | ≤60dB(Distance 1m) | ≤65dB(Distance 1m) | ||||||
size (W*D*Hmm) | 370×690×763 | 650×700×1600 | ||||||
Weight(kg) | 165 | 190 | 210 | 400 | 450 | 530 | 620 |
(3) Single into single out and three into single out general technical parameter
Single into single out and three into single out general technical parameter | ||
Input | frequency | 50Hz/60Hz±10% |
Power factor | ≥80% | |
Output | Voltage | 220V±1% |
Voltage adjustment | Regulated±1%,dynamic±2%,(0-100% load change < 20 ms) | |
Frequency stability | 50Hz/60Hz±0.5%(battery powered) | |
Frequency torsional rate | Less than 1 hz/sec. | |
Harmonic distortion | Linear load is less than 3% (load), rectifier total harmonic is less than 5% | |
Overload capacity | 130% | |
waveform | Wave form | |
efficiency | Input AC to output AC | More than 95% |
transfer time | Transfer between mains and battery | 0 seconds |
Transfer between inverter and bypass | Less than 4 millisecond | |
battery | type | Lead-acid seal free maintenance |
Charging time | After completely discharge 8 hours and charged to 90% | |
Alarm song | Overload load | Output overload, tweet once every 1 second |
Output severe overload protection, continuous tweets | ||
Battery discharge | Mains power supply failure, tweet once every 4 seconds | |
Battery low voltage beep once every 1 second | ||
The battery discharge will stop, continuous chirping | ||
Fault anomaly | continuous chirping | |
Protection performance | battery | Battery low energy automatic to jump to BYPASS,after the battery saturation automatically recovery |
overload | Overload (120 ~ 150%) 30 seconds later automatic to jump to BYPASS, automatic recovery | |
Over temperature | Inverter internal temperature > 85 ºC, automatic to jump to BYPASS | |
Output short circuit | The current limit and automatic shutdown, fuse and no fuse switch protection | |
Inverter anomaly | Automatic to jump to BYPASS and the mains supply | |
LCD display | LCD display information | Display input and output voltage, frequency, battery voltage, output load |
environment | temperature | -10~50ºC( |
Relative humidity | 20% to 93% (non-condensing) | |
altitude | Altitude 1000m or less |
Warranty:
Quality warranty for 1 year; parts will be shipped free during warranty period.
Delivery time:
Stick to contract.