400KVA Standby Diesel Generator Set (Cummins NTAA855-G7A)

Loading Port:Shanghai

Payment Terms:TT OR LC

Min Order Qty:1 set

Supply Capability:1000 set/month

Product Description:

400KVA Diesel Generator Set used as standby and emergency power

 

1. Features

1) Universal design and manufacture

2) Most widely used around the world

3) With most service terminals

4) Engineers are familiar with Cummins powered gensets

5) You could find spare-parts very easy


2. Technical Specifications


Technical Specifications

Genset model

SCE440

Genset rated power

320KW/400KVA 

Rated voltage

230/400V (adjustable)

Rated current

576 Amps

Frequency

50 Hz

Power factor

0.8 Lagging

Connecting type

3 phase 4 wire

Cooling system

Closed cycle water-cooled with fan, water tank

Overall dimension (L×W×H) mm

3600×1000×1950

Gross weight (kg)

3700

Diesel Engine

Brand

CCEC CUMMINS

Model

NTAA855-G7A

Engine type

6 cylinders in line,4 stroke, air-air after-cooled

Aspiration

Turbocharged

Rotating speed

1500 RPM

Engine cooling system

Water-cooled

Speed governing system

Electronic speed governor

Starting method

By 24V batteries 

Engine filter system

Dry type air filter ,fuel filter, oil filter, water filter

Displacement(L)

14

Bore×Stroke(mm)

140×152

Compression ratio

14.0: 1

100% Load fuel consumption (l/h)

75.6

Lube capacity(L)

33.4

Alternator

Brand

ENGGA

Model

EG315-320N

Excite type

Brushless self-excited AVR regulation

Connecting type

3 phase 4 pole

Steady frequency change

0.50%

No load voltage

≥95%-105%

Steady voltage

≤±1%

Insulation class

Class H

Protection grade

IP21

The components of the genset

(1) Diesel engine; (2) Alternator; (3) Water tank & radiator assembly; (4) Control panel; (5) Base frame.



3. INSPECTION AND TEST

1 GENERAL

1.1 Each engine shall be tested at manufacturer’s workshop to certify the engine output and fuel consumption in accordance with the site operating condition specified by purchaser on the specification datasheet.

1.2 All relevant information drawings pertinent to the testing and test procedure shall be transmitted to the purchaser in advance of the test date notification.

1.3 The purchaser shall call for additional testing if test results are unsatisfactory or marginal. Any equipment rejected shall be repaired or replaced to the purchaser’s satisfaction and tests shall be repeated.

1.4 Any unsatisfactory material, equipment, installation, or workmanship shall be replaced or repaired to the purchasers satisfaction at the manufacturers cost.

1.5 The engine and generator shall be tested individually in accordance with relevant standards specified above.

1.6 The completed and individually tested engine and generator shall be assembled onto the base plate with all auxiliaries, instruments and controls for a complete test of the generator set.


400KVA Standby Diesel Generator Set (Cummins NTAA855-G7A)