35kV or Lower XLPE Insulation Power Cable

Loading Port:Shanghai

Payment Terms:TT OR LC

Min Order Qty:100 m

Supply Capability:10000 m/month

Product Description:

1.      Application 

It is used to transmit and distribute power in power transmission and distribution system of 6~35kV. It is generally applied to the fields including power, construction, mines,metallurgy, petrochemical industry and communications. And it is used as replacement of oil-immersed paper insulated power cable and partially as replacement of PVC insulated power cable. 


2.      Type and Specification 

 Voltage

6/6 kV、6/10 kV、8.7/10 kV、8.7/15 kV、21/35 kV、26/35 kV

 Type

YYJV62、YJLV62、YJV63、YJLV63、YJV72、YJLV72、YJV73、YJLV73、YJV、YJLV、YJY、YJLY、YJV22、YJLV22、YJV23、YJLV23、YJV32、YJLV32、YJV33、YJLV33、YJV42、YJLV42、YJV43、YJLV43

Size

(mm2)

1 Core: 25~1000;

3 Core: 25~500

Standard

GB/T 12706-2008


3.      Using features

①      Rated voltage Uo/U includes 0.6/1kV, 1.8/3kV, 3.6/6kV, 6/6kV, 6/10kV, 8.7/10kV, 12/20kV, 18/30kV, 21/35kV, 26/35kV. 

②      The highest allowed operating temperature of conductor for long-term working is 90℃. In short-circuit (Max. long-term is no more than 250℃) 

③      D.C. resistance of the conductor complies with the stipulations of GB/T 3956. 

④      Installation ambient temperature should be no lower than 0℃. Otherwise it should be preheated. The Min. bending radius should be no smaller than 15 times of cable outer diameter. 

⑤      The cable is laid without horizontal drop limit. 

⑥      Working Frequency Voltage Test:
   For cable with Uo of 3.6kV or lower: 2.5Uo+2kV/5min without puncture;
   For cable with Uo of 3.6kV~18kV or lower: 3.5Uo/5min without puncture;
   For cable with Uo of 21kV and 26kV: 2.5Uo/30min or 3.5Uo/5min without puncture. 

⑦      Partial Discharge Test: The discharge volume should be no more than 10Pc under 1.73Uo for the cable. There shall be no detectable discharge under the declared sensitivity test. 

 

4.      Picture of structure 


1、Conductor  2、Conductor shield   3、Insulation   4、Insulation shield   5、Copper tape shield   6、Filler   7、Tape   8、Inner sheath   9、Armor  10、Outer sheath