35kV or lower XLPE Insulation low smoke & low halogen flame-retardant Power Cable

Loading Port:Shanghai

Payment Terms:TT OR LC

Min Order Qty:100 m

Supply Capability:10000 m/month

Product Description:

1.      Application 

It is used to transmit and distribute power in power transmission and distribution system of 6~35kV. It is generally applied to the fields including power, construction, mines,metallurgy, petrochemical industry and communications. And it is used as replacement of oil-immersed paper insulated power cable and partially as replacement of PVC insulated power cable. 


2.      Type and Specification

  Voltage

6/6 kV、6/10 kV、8.7/10 kV、8.7/15 kV、21/35 kV、26/35 kV

 Type

DDZA-YJV、DDZA-YJLV、DDZB-YJV、DDZB-YJLV、DDZC-YJV、DDZC-YJLV、DDZA-YJV22(62)、

DDZA-YJLV22(62)、DDZB-YJV22(62)、DDZB-YJLV22(62)、DDZC-YJV22(62)、DDZC-YJLV22(62)、

DDZA-YJV32(72)、DDZA-YJLV32(72)、DDZB-YJV32(72)、DDZB-YJLV32(72)、DDZC-YJV32(72)、

DDZC-YJLV32(72)、DDZA-YJV42、DDZA-YJLV42、DDZB-YJV42、DDZB-YJLV42、DDZC-YJV42、

DDZC-YJLV42

 Specifications

(mm2)

1 Core: 25~1000;

3 Core: 25~500

Standard

GB/T 19666-2005、GB/T 12706-2008


3.      Using features

①      Rated voltage Uo/U includes0.6/1kV, 1.8/3kV, 3.6/6kV, 6/6kV, 6/10kV, 8.7/10kV, 12/20kV, 18/30kV, 21/35kV,26/35kV. 

②      The highest allowed operating temperature of conductor for long-term working is 90℃. In short-circuit (Max. long-term is no more than 250℃) 

③      D.C. resistance of the conductor complies with the stipulations of GB/T 3956. 

④      Installation ambient temperature should be no lower than 0℃. Otherwise it should be preheated. The Min. bending radius should be no smaller than 15 times of cable outer diameter. 

⑤      The cable is laid without horizontal drop limit. 

⑥      Working Frequency Voltage Test:: 
   For cable with Uo of 3.6kV or lower: 2.5Uo+2kV/5min without puncture; 
   For cable with Uo of 3.6kV~18kV or lower: 3.5Uo/5min without puncture; 
   For cable with Uo of 21kV and 26kV: 2.5Uo/30min or 3.5Uo/5min without puncture. 

⑦      Partial Discharge Test: The discharge volume should be no more than 10Pc under 1.73Uo for the cable. There shall be no detectable discharge under the declared sensitivity test. 

⑧      Flame-retardant Character:

The flame-retardant characteristics comply with GB/T 1996-2005. 


4.      Picture of structure


1、Conductor  2、Conductor shield   3、Insulation   4、Insulation shield   5、Copper tape shield   6、Filler  7、Tape    8、Inner sheath   9、Armor   10、Outer sheath