35kV or Lower XLPE Insulation low smoke& halogen-freeflame-retardant Power Cable

Loading Port:Shanghai

Payment Terms:TT OR LC

Min Order Qty:100 m

Supply Capability:10000 m/month

Product Description:

1.      Application

It is used to transmit and distribute power in power transmission and distribution system of 6~35KV. It is generally applied to the fields including power, construction, mines,metallurgy, petrochemical industry and communications. And it is used as replacement of oil-immersed paper insulated power cable and partially as replacement of PVC insulated power cable. 


2.      Type and Specification

Voltage

6/6 kV、6/10 kV、8.7/10 kV、8.7/15 kV、21/35 kV、26/35 kV

  Type

WDZA-YJY、WDZA-YJLY、WDZB-YJY、WDZB-YJLY、WDZC-YJY、WDZC-YJLY、WDZA-YJY23(63)、

WDZA-YJLY23(63)、WDZB-YJY23(63)、WDZB-YJLY23(63)、WDZC-YJY23(63)、WDZC-YJLY23(63)、

WDZA-YJY33(73)、WDZA-YJLY33(73)、WDZB-YJY33(73)、WDZB-YJLY33(73)、WDZC-YJY33(73)、

WDZC-YJLY33(73)、WDZA-YJY43、WDZA-YJLY43、WDZB-YJY43、WDZB-YJLY43、WDZC-YJY43、

WDZC-YJLY43

Size

(mm2)

1 Core: 25~1000;

3 Core: 25~500

Standard

GB/T 19666-2005、GB/T 12706-2008


3.      Using features

①      Rated voltage Uo/U includes 0.6/1kV, 1.8/3kV, 3.6/6kV, 6/6kV, 6/10kV, 8.7/10kV, 12/20kV, 18/30kV, 21/35kV, 26/35kV. 

②      The highest allowed operating temperature of conductor for long-term working is 90℃. In short-circuit (Max. long-term is no more than 250℃) 

③      D.C. resistance of the conductor complies with the stipulations of GB/T 3956. 

④      Installation ambient temperature should be no lower than 0℃. Otherwise it should be preheated. The Min. bending radius should be no smaller than 15 times of cable outer diameter. 

⑤      The cable is laid without horizontal drop limit.

⑥      Working Frequency Voltage Test::
   For cable with Uo of 3.6kV or lower: 2.5Uo+2kV/5min without puncture; 
   For cable with Uo of 3.6kV~18kV or lower: 3.5Uo/5min without puncture; 
   For cable with Uo of 21kV and 26kV: 2.5Uo/30min or 3.5Uo/5min without puncture.

⑦      Partial Discharge Test: The discharge volume should be no more than 10Pc under 1.73Uo for the cable. There shall be no detectable discharge under the declared sensitivity test. 

⑧      Flame-retardant Character:

The flame-retardant characteristics comply with GB/T 1996-2005. 

4.      Picture of structure


1、Conductor  2、Conductor shield   3、Insulation   4、Insulation shield  

 5、Copper tape shield   6、Filler  7、Tape    8、Innersheath   9、Armor   10、Outer sheath