1. Application
This product is suitable for termite damage zone in power plants, power stations and long-distance power transmission systems, especially in the high environmental requirements and pipe laying of underground power lines termite.
2. Type and Specification
Voltage | 6/6 kV、6/10 kV、8.7/10 kV、8.7/15 kV、21/35 kV、26/35 kV |
Type | FYS-WDZ-YJY、FYS-WDZ-YJY23、FYS-WDZ-YJY33、FYS-WDZ-YJY42、FYS-WDZ-YJLY、 FYS-WDZ-YJLY23、FYS-WDZ-YJLY33、FYS-WDZ-YJLY42 |
Size (mm2) | 1 Core: 25~1000; 3 Core: 25~500 |
Standard | Q/XLJ 0348 |
3. Using features
① Rated voltage Uo/U includes 0.6/1kV, 1.8/3kV, 3.6/6kV, 6/6kV, 6/10kV, 8.7/10kV, 12/20kV, 18/30kV, 21/35kV,26/35kV.
② The highest allowed operating temperature of conductor for long-term working is 90℃. In short-circuit (Max. long-term is no more than 250℃)
③ D.C. resistance of the conductor complies with the stipulations of GB/T 3956.
④ Installation ambient temperature should be no lower than 0℃. Otherwise it should be preheated. The Min. bending radius should be no smaller than 15 times of cable outer diameter.
⑤ The cable is laid without horizontal drop limit.
⑥ Working Frequency Voltage Test::
For cable with Uo of 3.6kV or lower: 2.5Uo+2kV/5min without puncture;
For cable with Uo of 3.6kV~18kV or lower: 3.5Uo/5min without puncture;
For cable with Uo of 21kV and 26kV: 2.5Uo/30min or 3.5Uo/5min without puncture.
⑦ Partial Discharge Test: The discharge volume should be no more than 10Pc under1.73Uo for the cable. There shall be no detectable discharge under the declared sensitivity test.
⑧ Flame-retardant Character:
The flame-retardant characteristics comply with GB/T 1996-2005
⑨ Cable prevention of rat and Termites characteristics comply with GB / T 2951.38-1986.
4. Picture of structure
1、Conductor 2、Conductor shield 3、Insulation 4、Insulation shield
5、Copper tape shield 6、Filler 7、Tape 8、Inner sheath 9、Armor 10、Outer sheath