Loading Port:China main port
Payment Terms:TT OR LC
Min Order Qty:1000 m
Supply Capability:20000 m/month
Standard
IEC 60502
Application
1kV copper conductor XLPE insulated power cable is used for fixed installations of rated voltages 1kV and below, such as distrubution networks or industrial installations. It can be installed in cable duct, trench or directly buried in earth.
Product Description
1) Rated Voltage: 600/1000V
2) Max. working temperature: 70 °c for pvc insulation and 90 °c for xlpe insulation
3) Max. temperature during short circuit (≤5S): 160°c (PVC insulation), 250°c (XLPE insulation)
4) Conductor: class 1 and 2 copper or aluminum
5) Shape of conductor: circular and sectional
6) Sectional area: 1.5 - 500mm2
7) Insulation: PVC / XLPE
8) No. of cores: 1, 2, 3, 3+1, 3+2, 4, 4+1, 5
9) Armor: steel wire or steel tape available
10) Sheath: PVC
11) Min. beding radius: 15 times cable radius (single core), 12 times cable radius (multi cores)
12) Max. conductor DC resistance at 20 °c
Sectional area (mm2) | 1.5 | 2.5 | 4 | 6 | 10 | 16 | 25 | 35 | 50 | 70 | 95 |
Copper (Ω/km) | 12.10 | 7.410 | 4.610 | 3.080 | 1.830 | 1.150 | 0.727 | 0.524 | 0.387 | 0.268 | 0.193 |
Aluminum (Ω/km ) | - | 12.1 | 7.41 | 4.61 | 3.08 | 1.91 | 1.20 | 0.868 | 0.641 | 0.443 | 0.320 |
Sectional area (mm2) | 120 | 150 | 185 | 240 | 300 | 400 | 500 | 630 | 800 | 1000 | 1200 |
Copper (Ω/km) | 0.153 | 0.124 | 0.0991 | 0.0754 | 0.0601 | 0.0470 | 0.0366 | 0.0283 | 0.0221 | 0.0176 | 0.0151 |
Aluminum (Ω/km ) | 0.253 | 0.206 | 0.164 | 0.125 | 0.100 | 0.0778 | 0.0605 | 0.0469 | 0.0367 | 0.0291 | 0.0247 |