0.6/1kV XLPE Insulation Low Smoke ZeroHalogen Flame Retardant Power Cable

Loading Port:Shanghai

Payment Terms:TT or LC

Min Order Qty:100 m

Supply Capability:10000 m/month

Product Description:

Introduction:

This product is apply to AC rated voltage 0.6/1kV circuit, for the use of power transmission and distribution, suitable for densely inhabited district with high-rise buildings, Shopping malls, etc. 

Specification:

 Voltage Class

 0.6/1 kV

 Type

WDZA-YJY、WDZA-YJLY、WDZB-YJY、WDZB-YJLY、WDZC-YJY、WDZC-YJLY、

WDZA-YJY23(63)、WDZA-YJLY23(63)、WDZB-YJY23(63)、WDZB-YJLY23(63)、

WDZC-YJY23(63)、WDZC-YJLY23(63)、WDZA-YJY33(73)、WDZA-YJLY33(73)、

WDZB-YJY33(73)、WDZB-YJLY33(73)、WDZC-YJY33(73)、WDZC-YJLY33(73)、

WDZA-YJY43、WDZA-YJLY43、WDZB-YJY43、WDZB-YJLY43、

WDZC-YJY43、WDZC-YJLY43

 Size Range(mm2)

1 core:1.5~1000;
 2 cores:1.5~500;
 3 cores:1.5~500;
 4 cores:1.5~500;
 5 cores:4~500;
 3+1 cores:4~500;
 3+2 cores:4~500;
 4+1 cores:4~500 。

Executive Standard

 GB/T 19666-2005、GB/T 12706-2008

 

Features:

     a. Cable conductor allowed long-term working temperature not exceeding 90 ℃. 

        When short circuit happened (the duration no longer than 5 seconds), the maximum temperature of cable conductor is not exceeding 250℃.

     b. When laying cable, the ambient temperature should not be lower than 0℃,if not the cable need to be preheated. The bending radius of three cores unarmored cable should not be less than 15 times of outer diameter of cable, 12 times for armored cable. The bending radius of single core unarmored cable should not be less than 20 times of outer diameter of the cable, 15 times for armored cable. 

     c. Cable DC resistance should comply with GB/T3956-1997.

     d. The laying of cable is not limited by the level drops.

     e. Power frequency voltage withstanding test: U0 under 3.6kV,2.5 U0 +2kV/5min no breakdown.

     f. Partial discharge test: discharge capacity under 1.73U0 is not more than 10pC.

     e. The cable should withstand group burning test specified in GB/T18380.3-2001, and combustion smoke density should comply with the regulations ofGB/T19666-2005.Combustion product gas water solution PH value≥4.3, electric conductivity≤10us/mm.