0.6/1kV XLPE Insulated Power Cable
The cable meets the standard requirements of GB/T12706-2002 or IEC60502-1997.
0.6/1kV XLPE Insulated Power Cable |
1.Standards
3.Specifications TypeNumber of coresNominal Cross-sectional Area(mm2)YJV YJLV11.0~630YJV YJV22YJLV YJLV2221.0~400YJV YJV22YJLV YJLV2231.0~400YJV YJV22YJLV YJLV223+14.0~400YJV YJV22YJLV YJLV2241.0~400YJV YJV22YJLV YJLV2251.0~400 |
4.Using properties
1.The maximum rated temperature
The maximum operating temperature of cores shall not exceed 90°C when the cable is used for long period. The temperature of cores shall not exceed 250°C at short circuit for 5 seconds.
2,The installation of cables is not limited by the difference of level along the route. The ambient temperature should not be below 0°C during installation. The permissible bending radius for cable shall not be less than 10 times of the cable diameter. The single cable shall be without amour or with steel wire amour when it is electrified with alternating current and shall not be laid in magnetic ducts.
5.Technical specifications
Rated voltage of cable | 0.6/1kV |
D.C. resistance of core | According to GB/T3856-1997 or IEC228A-82 |
Power frequency withstand voltage test for 5 minutes(KV) | No breakdown at 3.5kV |
Hot set test for insulation, 200°C 15min with pressure 20N/cm2 | |
Maximum elongation values at load | 175% |
Maximum permanent elongation values after being cooled | 15% |
Power frequency withstand voltage test for 4 hours, not break down | 2.4 |
6.Technical parameters
YJV, YJLV 0.6/1kV