SUN-10/12/15K-G03-LV | 10-15KW | Three Phase | 2 MPPT | Low Voltage | 127/220Vac

Loading Port:Ningbo

Payment Terms:TT OR LC

Min Order Qty:100 pc

Supply Capability:5000 pc/month

Product Description:

Technical Data
Model                                                                                        SUN-10K-G03-LV                                               SUN-12K-G02-LV                                                  SUN-15K-G02-LV
Input Side
Max. DC Input Power (kW)1315.619.5
Max. DC Input Voltage (V)800
Start-up DC Input Voltage (V)250
MPPT    Operating Range (V)200~700
Max. DC Input Current (A)32+32
Max. Short Circuit Current (A)48+48
Number of MPPT / Strings per MPPT2/2
Output Side
Rated Output Power (kW)101215
Max. Active Power (kW)1113.216.5
Nominal Output Voltage / Range (V)3L/N/PE 127/0.85Un-1.1Un220 /0.85Un-1.1Un (this may vary with grid standards)
Rated Grid Frequency (Hz)60 / 50 (Optional)
Operating PhaseThree phase
Rated AC Grid Output Current (A)26.231.539.4
Max. AC Output Current (A)28.934.643.3
Output Power Factor0.8 leading to 0.8 lagging
Grid Current THD<3%
DC Injection Current (mA)<0.5%
Grid Frequency Range57~62
Efficiency
Max. Efficiency98.6%
Euro Efficiency98%
MPPT Efficiency>99%
Protection
DC Reverse-Polarity ProtectionYes
AC Short Circuit ProtectionYes
AC Output Overcurrent ProtectionYes
Output Overvoltage ProtectionYes
Insulation Resistance ProtectionYes
Ground Fault MonitoringYes
Anti-islanding ProtectionYes
Temperature ProtectionYes
Integrated DC SwitchYes
Remote software uploadYes
Remote change of operating parametersYes
Surge protectionDC Type II / AC Type II
General Data
Size (mm)330W×508H×206D
Weight (kg)20.8
TopologyTransformerless
Internal Consumption<1W (Night)
Running Temperature-25~65,   >45 derating
Ingress ProtectionIP65
Noise Emission (Typical)<45 dB
Cooling ConceptSmart cooling
Max. Operating Altitude Without Derating2000m
Warranty5 years
Grid Connection StandardCEI 0-21, VDE-AR-N 4105, NRS 097, IEC 62116, IEC 61727, G99,   G98, VDE 0126-1-1, RD 1699, C10-11
Operating Surroundings Humidity0-100%
Safety EMC / StandardIEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2
Features
DC Connection
    AC Connection Display
    Interface
MC-4 mateable
   
AC ConnectionIP65 rated plug 
DisplayLCD1602 
InterfaceRS485/RS232/Wifi/LAN

This series inverter is specially designed for 127/220Vac three-phase system, especially suits for South American areas. With compactness design, easy to install and operate. It supports wide AC output voltage to adapt to poor grid, extending the inverter working hours.