Online UPS, CE certificate 19 inch rack-mount

Loading Port:Shekou

Payment Terms:TT OR LC

Min Order Qty:100 pc

Supply Capability:99999 pc/month

Product Description:

Online UPS, CE certificate 19 inch rack-mount

 

Specifications

1,UPS, online UPS rack mount type, 
2,Wide input range dual conversion 
3,IGBT technology, Advanced PFC technology 

Rack Online UPS, CE certificate

 

UPS, online UPS rack mount type, wide input range, dual conversion, IGBT technology, Advanced PFC technology, self-detection, provide reliable uninterruptible power to your instrument.

 

Features:

 

1.19 inch rack-mount

2. High frequency and dual conversion online technology

3. Advanced PFC technology

4. True sine wave output with less then 3%THD

5.Self-detection when UPS start-up

6. Advanced battery management

7.Cold start feature(DC power on)

8. Automatically charging batteries in UPS off mode

9. Lighting and surge protections(surge energy rating 1050Joules)

10. Short circuit and overload protections

11. Fun speed automatically changes as load varies

12. Optional external battery pack

13. EMI/RFI noise filter

14. Shutdown and restart schedule

 

Product Series

Bs-R Series Rack Mount 1~6kVA

Model

Bs-R 1K

Bs-R 2K

Bs-R 3K

Bs-R 6K

Rated Power

VA/W

1kVA / 0.7kW

2kVA / 1.4kW

3kVA / 2.1kW

6kVA/4.2kW

Input

Nominal Voltage

220VAC/110vac

220VAC

Voltage Range

115 ~ 300VAC/60~138 Vac

176 ~ 276VAC

Frequency Range

46 ~ 54Hz(default), user adjustable within 40~60Hz

46 ~ 54Hz

Power Factor

0.97

0.98

Connection

IEC320-10A inlet

IEC320-16A inlet

Terminal Block

Output

Voltage

220VAC/110vac ± 2%

220VAC ± 1%

Frequency

46~54Hz or 50Hz ± 0.2Hz (Line mode)
50Hz ± 0.2Hz ( Battery mode)

46~54Hz (Line mode)
50Hz ± 0.05Hz ( Battery mode)

Waveform

Sine Wave

Overload Capability

108%~150% for 30 sec., ³150% for 300 ms

105%~130% for 10 min., ³130% for 1 min.

Current Crest Ratio

3:1

Bypass

Automatic Transfer

on overload and UPS failure

Before UPS Power-on

Default NO, user adjustable to YES

Yes

Voltage Range 

80~264VAC (Default), user adjustable within 80~286VAC

176 ~ 261VAC

Transfer Time

0 ms; less than 4 ms from inverter to bypass and vice versa

Zero

LED indicators

Status

Load level / Battery level, Battery , Utility Power, Inverter, Bypass, Overload, Fault

Audible Alarm

Bypass, On battery mode, Battery low, Overload, Fault

Communications

RS-232 Serial Interface

Intelligent Slot;
OPTIONS:  WEBPOWER SNMP/WEB card, AS400 card or WinPower CMC)

Network Surge Protection

RJ45 I/O port available for network or Fax/Modem

Environmental

Operating Temperature

0 ~ 40°C

Operating Humidity

20 ~ 90% non-condensing

Main Unit

Net Weight (Kg)

15.3

10.3

11.2

18.3

Dimensions (W x D x H) mm

482.6 x 450 x 88 (2U)

482.6 x 600 x 130 (3U)

Battery Pack

Type

Internal Batteries

External Battery Pack

Nominal DC Voltage

36VDC

96VDC

240VDC

Backup Time (Full load)

5 min

9 min
(with 1 BP)

5 min
(with 1 BP)

7 min
(with 1 BP)

Net Weight (Kg)

--

Dimensions (W x D x H) mm

450x482.6x88 (2U)

450x482.6x88 (2U)

482.6 x 600 x 130 (3U

 

Online UPS, CE certificate 19 inch rack-mount

 

                       Online UPS, CE certificate 19 inch rack-mount